This guide provides step-by-step installation instructions for the Veris Z203392-0C 10A SPST enclosed relay. It includes wiring diagrams, color-coded connections, and safety warnings. The relay is rated for 10A at 277VAC and features a resistive HOA monitor for position feedback. Installation must be performed by qualified personnel and requires disconnecting power before work.

The guide specifies coil and contact ratings, mounting dimensions, and programming ranges for the resistive monitor. Safety precautions include following NFPA 70E standards and ensuring proper enclosure mounting. Failure to follow instructions may result in electric shock or injury.

What's inside

  • Installation Steps
  • Wiring Diagram
  • Color Code Specifications
  • Relay Ratings
  • HOA Monitor Programming
  • Safety Warnings
  • Mounting Dimensions

Specifications

Operating Temperature-40° to 55°C (-40° to 131°F)
Operating Humidity10-90% RH, non-condensing
Electrical Relay Life100,000 cycles
Mechanical Relay Life10,000,000 cycles
Coil Voltage (Low)10-30VAC/DC
Coil Voltage (High)120VAC
Contact Rating10A@277VAC
Insulation Class600VAC RMS
Agency ApprovalsUL508 enclosed device listing, pollution degree 2

Frequently asked questions

What is the maximum voltage for the resistive HOA monitor?

Maximum voltage is 13.4VAC/DC.

What is the mounting dimension for the relay?

The relay has a 2.0" (52 mm) width and 2.5" (64 mm) height with a 3/4" NPT nipple.