Installation guide for Veris Z203392-0C 10A SPST enclosed relay with wiring, specs, and safety instructions.
This guide provides step-by-step installation instructions for the Veris Z203392-0C 10A SPST enclosed relay. It includes wiring diagrams, color-coded connections, and safety warnings. The relay is rated for 10A at 277VAC and features a resistive HOA monitor for position feedback. Installation must be performed by qualified personnel and requires disconnecting power before work.
The guide specifies coil and contact ratings, mounting dimensions, and programming ranges for the resistive monitor. Safety precautions include following NFPA 70E standards and ensuring proper enclosure mounting. Failure to follow instructions may result in electric shock or injury.
| Operating Temperature | -40° to 55°C (-40° to 131°F) |
|---|---|
| Operating Humidity | 10-90% RH, non-condensing |
| Electrical Relay Life | 100,000 cycles |
| Mechanical Relay Life | 10,000,000 cycles |
| Coil Voltage (Low) | 10-30VAC/DC |
| Coil Voltage (High) | 120VAC |
| Contact Rating | 10A@277VAC |
| Insulation Class | 600VAC RMS |
| Agency Approvals | UL508 enclosed device listing, pollution degree 2 |
Maximum voltage is 13.4VAC/DC.
The relay has a 2.0" (52 mm) width and 2.5" (64 mm) height with a 3/4" NPT nipple.