Veris H906 current monitoring installation guide covering specifications, wiring, mounting, calibration, and troubleshooting for the split-core current switch.
The H906 is a current-sensitive switching device that monitors current in a conductor passing through it and provides an N.C. status output for building controllers or data acquisition equipment. It requires a 5-30VDC external power supply and has an adjustable setpoint controlled by a twenty-turn potentiometer.
This guide includes installer specifications, wiring and mounting information, calibration procedures for under-current and over-current monitoring, and troubleshooting steps for common installation issues.
| Sensor power | 5-30VDC |
|---|---|
| Insulation class | 600VAC RMS (UL), 300VAC RMS (CE) |
| Frequency range | 50/60Hz |
| Temperature range | -15° to 60 °C (5° to 140 °F) |
| Humidity range | 10-90% RH non-condensing |
| Hysteresis | 10% of setpoint, typical |
| Off-state leakage | 34μA@5VDC, 200μA@30VDC |
| On-state voltage drop | 1.9VDC [email protected] |
| Amperage range | 2.5 - 135A Continuous |
| Output | N.C. 0.1A@30VDC, polarity sensitive |
| Safety | UL 508, IEC 61010-1: 2001 CAT III |
The H906 requires a 5-30VDC external power supply to generate its output.
Wrap the monitored conductor through the center hole and around the sensor body to produce multiple turns through the window.
Check sensor calibration, control voltage at the sensor, amperage in the monitored conductor, and ensure the sensor core mating surfaces are clean and the core clamp is completely closed.
The setpoint is adjustable through the action of a twenty (20) turn potentiometer.