Veris H6810, H6811, H6812 5 Amp Split-Core Current Transformer Installation Guide

Installation guide for Veris H6810, H6811, and H6812 5 A split-core current transformers, with ratings, accuracy, and dimensions.


Veris H6810, H6811, H6812 5 Amp Split-Core Current Transformer Installation Guide - cover page
Brand
Veris
Category
transformers
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
535 KB
Published
20 November, 2026
Updated
20 November, 2026
MD5 checksum
24EED621D2AE23E119D32A5B54BA60D1

About this manual

Veris H6810, H6811, and H6812 are 5 A split-core current transformers for use with power meters, data loggers, chart recorders, and other instruments. The guide covers installation, safety warnings, ratings, accuracy, and dimensions.

Installation requires disconnecting and locking out power, connecting secondary leads to the burden or shorting bar, opening and closing the split core over the primary conductor, checking core ends, and mounting the transformer securely.

What's inside

  • Installer's Specifications
  • Product Identification
  • Installation
  • Notes
  • Operation
  • Ratings
  • Accuracy
  • Dimensions

Specifications

Output at rated current5 Amps AC
Leads18 AWG, UL 1015 twisted pair, 6 ft (1.8 m) standard length
Operating temperature range-15 to 60 C (5 to 140 F)
Storage temperature range-40 to 70 C (-40 to 158 F)
Humidity range0-95% noncondensing
Maximum voltage L-N sensed conductor600 VAC (basic insulation rating)
Frequency range50/60 Hz
Altitude of operation3 km max.
Installation categoryCat II or Cat III
H6810 sensing current0 to 300 A
H6811 sensing current0 to 800 A
H6812 sensing current0 to 2400 A

Frequently asked questions

What is the output current at rated current?

The H6810, H6811, and H6812 provide 5 Amps AC at rated current.

What is the maximum voltage without additional insulation?

The maximum voltage without additional insulation is 600 VAC for the H6810, H6811, and H6812.

How must the secondary leads or terminals be handled?

They must be shorted or connected to the burden at all times.

Download PDF (535 KB)