Installation guide for the Veris G Series carbon monoxide detector and fan controller, with specifications, wiring, mounting, service and troubleshooting.
This installation guide covers the Veris G Series carbon monoxide detector, a transmitter and fan controller that measures CO levels and signals control systems to provide an inlet of fresh air for the space. It includes product identification, specifications, dimensions, wiring, mounting, sensor replacement and troubleshooting.
The G Series is offered in duct-mount and wall-mount versions with a selectable 4-20 mA or 0-5/0-10 V analog output and an optional auxiliary alarm. It uses a replaceable metal oxide semiconductor sensor with a 5-10 year typical life and sounds an 85 dB alarm when the CO level exceeds 100 ppm for 30 minutes.
| Input Power | 15-30VDC/24VAC, 0.3A@24VAC |
|---|---|
| Sensor Type | Digitally profiled metal oxide semiconductor (MOS) |
| Sensor Life | 5-10 years typical, replaceable |
| Detection Range | 0 to 200 ppm |
| Analog Output | 3-wire sourcing, 4-20mA or user selectable 0-5V/0-10V |
| Relay Output | N.O. Form A (SPST) 8A@30VAC/VDC |
| Relay Setpoint | 25 ppm |
| High Limit Alarm | Audible, 85 dB, resets below 100 ppm |
| Operating Temperature Range | -20° to 50°C (-4° to 122°F) |
| Coverage | 5000-7500 sq ft typical (465-697 sq m) |
The relay contact closes when the CO level is below 25 ppm and opens when it is above 25 ppm; removal of the sensor, power interruption, or cut wires also opens the relay circuit and starts the fan.
An 85 dB alarm sounds if the CO level rises above 100 ppm for 30 minutes and resets below 100 ppm.
Replace the sensor module every five years with a Veris Industries CO sensor replacement module, part number AA09.
No. The sensor module is factory calibrated and no field calibration is required or possible; a replacement sensor needs 96 hours to stabilize after power is applied.