Veris G Series Carbon Monoxide Transmitter and Fan Controller Installation Guide

Installation guide for the Veris G Series carbon monoxide detector and fan controller, with specifications, wiring, mounting, service and troubleshooting.


Veris G Series Carbon Monoxide Transmitter and Fan Controller Installation Guide - cover page
Brand
Veris
Category
sensor
Document type
Installation Guide
Language
English
Pages
3
File format
PDF
File size
639 KB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
0F8861DF21F16647DD6E6F7B2E44DC51

About this manual

This installation guide covers the Veris G Series carbon monoxide detector, a transmitter and fan controller that measures CO levels and signals control systems to provide an inlet of fresh air for the space. It includes product identification, specifications, dimensions, wiring, mounting, sensor replacement and troubleshooting.

The G Series is offered in duct-mount and wall-mount versions with a selectable 4-20 mA or 0-5/0-10 V analog output and an optional auxiliary alarm. It uses a replaceable metal oxide semiconductor sensor with a 5-10 year typical life and sounds an 85 dB alarm when the CO level exceeds 100 ppm for 30 minutes.

What's inside

  • Product Identification
  • Product Overview
  • Specifications
  • Dimensions
  • Installation
  • Service
  • Troubleshooting

Specifications

Input Power15-30VDC/24VAC, 0.3A@24VAC
Sensor TypeDigitally profiled metal oxide semiconductor (MOS)
Sensor Life5-10 years typical, replaceable
Detection Range0 to 200 ppm
Analog Output3-wire sourcing, 4-20mA or user selectable 0-5V/0-10V
Relay OutputN.O. Form A (SPST) 8A@30VAC/VDC
Relay Setpoint25 ppm
High Limit AlarmAudible, 85 dB, resets below 100 ppm
Operating Temperature Range-20° to 50°C (-4° to 122°F)
Coverage5000-7500 sq ft typical (465-697 sq m)

Frequently asked questions

What does the relay contact do?

The relay contact closes when the CO level is below 25 ppm and opens when it is above 25 ppm; removal of the sensor, power interruption, or cut wires also opens the relay circuit and starts the fan.

When does the audible alarm sound?

An 85 dB alarm sounds if the CO level rises above 100 ppm for 30 minutes and resets below 100 ppm.

How often should the sensor module be replaced?

Replace the sensor module every five years with a Veris Industries CO sensor replacement module, part number AA09.

Does the sensor need field calibration?

No. The sensor module is factory calibrated and no field calibration is required or possible; a replacement sensor needs 96 hours to stabilize after power is applied.