Veris H609 Current Monitor Installation Guide

Installation and calibration instructions for the Veris H609 Split-Core Current Switch, including wiring, mounting, and setpoint adjustment.


Veris H609 Current Monitor Installation Guide - cover page
Brand
Veris
Category
Other Electronics
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
972 KB
Published
05 November, 2026
Updated
05 November, 2026
MD5 checksum
1118C7747D316D9B3D86DEDAC43AA6AB

About this manual

This document serves as an installation guide for the Veris H609 Split-Core Current Switch, a current-sensitive switching device designed to monitor amperage in conductors. It is intended for use by qualified electrical personnel and covers safety warnings, installation steps, and operational details.

What's inside

  • Installer's Specifications
  • Safety Warnings
  • Wiring Example
  • Dimensions
  • Installation
  • Operation
  • Troubleshooting
  • Calibration

Specifications

Amperage Range1.25-50 A
External Supply VoltageInduced from monitored conductor
Frequency50/60 Hz
Temperature Range-15 ° to 60 °C
Humidity Range10-90% RH non-condensing
Hysteresis10% typical
Status Output RatingsN.O. 0.2 A@120 VAC/DC
Terminal Block Max. Wire Size14 AWG
Insulation Class600 VAC RMS (UL)

Frequently asked questions

Does the H609 require an external power supply?

No, the H609 requires no external power supply to generate its output.

What is the maximum wire size for the terminal block?

The maximum wire size for the terminal block is 14 AWG.

How do I reset the sensor if the setpoint screw has no stops?

Turn the setpoint screw 20 turns counter-clockwise to reset the sensor to be most sensitive.