Installation instructions for Veris CW Series wall-mount CO2 sensors with optional RH and temperature measurement.
The Veris CW Series Installation Guide covers wall-mount environmental CO2 sensors that measure CO2 levels, with optional relative humidity and temperature sensing for air inside a duct. The CWL and CWE models support field calibration and a five-year CO2 calibration interval.
The guide includes mounting and wiring instructions, output scaling tables, ABC automatic baseline calibration settings, and specifications for the CO2, RH, and temperature transmitters.
| Input Voltage | Class 2; 20 to 30 Vdc, 24 Vac |
|---|---|
| Sensor Current Draw | 100 mA max. |
| Operating Temperature Range (no humidity) | 0 to 50 °C (32 to 122 °F) |
| Operating Humidity Range | 0 to 95% (non-condensing) |
| Housing Material | High impact ABS plastic |
| CO2 Output Range (CWL) | 0 to 2000 ppm or 0 to 5000 ppm |
| CO2 Accuracy | ±30 ppm ±2% of measured value |
| Temperature Accuracy | ±0.5 °C (±1 °F) typical |
The CO2 sensor operates within accuracy specifications for an interval of five years and can be field calibrated.
ABC automatically adjusts the CO2 sensor to compensate for drift over a running 7-day or 28-day period.
Position the sensor vertically on the wall, 4-1/2 feet above the floor, away from windows, vents, and drafts.
No, the Pushbutton Override feature is not available with temperature transmitter models.