TECO 7200MA frequency inverter MODBUS RS-485 communication application manual covering parameters, wiring, message formats, and fault handling.
This manual describes the communication methods between the TECO 7200MA frequency inverter and host controllers such as PCs and PLCs. It covers the RS-485 interface, MODBUS RTU protocol, communication format, transfer speed, parity, and related inverter parameters.
It also explains wiring terminals, inverter return messages, message formats for read, loop test, and write commands, CRC-16 generation, communication status indication, and communication fault handling with connection examples. This manual is written in Chinese.
| Interface | RS-485 |
|---|---|
| Protocol | MODBUS RTU mode |
| Transfer speed | 1200/2400/4800/9600 bps |
| Parity | No parity/even parity/odd parity |
| Node address range | 1~31 (default 1) |
| Supported function codes | 03H, 08H, 10H |
It supports 1200, 2400, 4800, or 9600 bps, set by parameter Sn-37.
The default node address is 1, and Sn-36 can set addresses from 1 to 31.
It supports 03H Read Data from Holding Register, 08H Loop Test, and 10H Write Data to Holding Register.