Product manual for the PR electronics 5116 programmable transmitter covering safety, installation, connections, configuration, and specifications.
This is the product manual for the PR electronics 5116 programmable transmitter. The device has inputs for RTD, TC, mV, Ohm, potentiometer, mA and V signals, a 2-wire supply greater than 16.5 V, and outputs for current, voltage and two relays. It can use a universal AC or DC supply and is mounted on a DIN rail.
The manual covers warnings and safety instructions, including instructions for intrinsically safe installation of the 5116B, and how to demount SYSTEM 5000. It also describes the application, technical characteristics, mounting and installation, electrical specifications, connections, block diagram, relay actions, connection to Loop Link, activation of the process calibration button, relay configuration in PReset, process calibration, error functions, and the appendix.
| Supply | 21.6...253 VAC or 19.2...300 VDC |
|---|---|
| Galvanic isolation | 3-port 3.75 kVAC |
| 2-wire supply | > 16.5 V |
| Output signals | Relays, analog 0/4...20 mA and voltage |
| Maximum ambient temperature | 60°C |
| Maximum wire size | AWG 26-14 |
| Insulation class | Class II |
| Pollution degree | 2 |
| Mounting | DIN rail according to DIN 46277 |
| Devices per metre | Up to 42 |
It supports RTD, TC, mV, Ohm, potmeter, mA and V input signals.
The supply can be 21.6...253 VAC or 19.2...300 VDC.
It is mounted vertically or horizontally on a DIN rail.
Up to 42 devices can be mounted per metre.