PR electronics 4184 Universal Mono/Bi-Polar Signal Transmitter Installation Guide

The 4184 Universal Mono/Bi-Polar Signal Transmitter is a 6 mm isolation device developed on microprocessor technology, which is compact, responsive and high quality, providing excellent performance and anti-electromagnetic interference for dedicated applications at an extremely low total cost of ownership. It can be installed horizontally or vertically, and there is no gap between devices.


PR electronics 4184 Universal Mono/Bi-Polar Signal Transmitter Installation Guide - cover page
Brand
PR electronics
Category
Other Electronics
Document type
Installation Guide
Language
Chinese
Pages
34
File format
PDF
File size
2 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
A690431FA6B23F058A43987AD5DC1EDF

About this manual

This document is the Chinese installation guide (document no. 4184V103-CN) for the PR electronics 4184 universal mono/bi-polar signal transmitter from the 4000 series of 6 mm isolators. It describes a microprocessor-based module that measures DC voltage and current inputs up to ±300 V / ±100 mA with a minimum measurement range down to 25 mV / 0.5 mA, and provides passive/active current outputs and buffered voltage outputs. The 4184 is designed for SIL 2 installations and systems with performance level (PL) "d" according to ISO-13849.

The guide covers safety instructions and warnings, mounting and removal of 4000 series modules on DIN rails, applications, technical characteristics, wiring, the detachable PR 4500 display/programming panel, configuration and operation keys, menu flowcharts including advanced settings, and a document revision history. All parameters are password protected, and the PR 4500 panel can be moved between devices to download configurations. This manual is written in Chinese.

What's inside

  • 警告 (Warning)
  • 符号含义 (Symbol meanings)
  • 安全须知 (Safety instructions)
  • 如何拆装 4000 系列产品 (Mounting and removal of 4000 series)
  • 应用 (Applications)
  • 技术特点 (Technical characteristics)
  • 安装调试 (Installation and commissioning)
  • PR 4500 显示/编程面板 (PR 4500 display/programming panel)
  • 接线方式 (Wiring)
  • 菜单流程图 (Menu flowchart)

Specifications

Input measurement rangeup to ±300 V DC / ±100 mA, minimum range 25 mV / 0.5 mA
Response time< 20 ms
Accuracy< 0.05%
Power supply21.6...253 VAC / 19.2...300 VDC
Current output loadup to 1000 ohm
Adjustable response time0.0...60.0 s
Signal-to-noise ratio> 60 dB
Isolation test2.3 kVAC, 3-port
UL file numberE248256
Maximum ambient temperature (UL)60°C

Frequently asked questions

What power supply can the 4184 be operated with?

The 4184 accepts a universal supply of 21.6...253 VAC or 19.2...300 VDC.

Is the 4184 suitable for SIL 2 applications?

Yes, the 4184 is designed to strict safety requirements and is suitable for SIL 2 installations, as well as systems with performance level "d" per ISO-13849.

How is the 4184 mounted?

The 4000 series must be mounted on a DIN rail according to DIN EN 60715; the module can be installed side by side without clearance.

Can a display be attached to the 4184?

Yes, the detachable PR 4500 display/programming panel provides parameter configuration, process monitoring, 2-point process calibration and enhanced diagnostics.

Download PDF (2 MB)