Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual

Hongrun NHR-A31 series current input isolated safety barrier user manual: specifications, certification parameters, wiring diagrams and setup.


Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual - cover page
Brand
Hong Run
Category
Other
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
836 KB
Published
09 November, 2026
Updated
09 November, 2026
Model
NHR-A31
MD5 checksum
1D740294645C55DC7625AB33A0FD6EB8

About this manual

The NHR-A31 series current input isolated safety barrier converts current signals from the hazardous area into voltage, current, RS485 or switch signals and transmits them in isolation to the safe area. The unit requires an independent power supply and provides three-way isolation between input, output and power. It is tested to GB/T 3836.1-2021 and GB/T 3836.4-2021, holds a CCC certificate and can be used with intrinsically safe equipment in Zone 0, 1 and 2 hazardous gas areas. It mounts on a 35 mm DIN rail and has a working indicator that is green during normal operation and red for a fault signal.

This Chinese-language user manual covers the product introduction, panel and structure diagram, model selection table, technical parameters, certification parameters, matching principles for intrinsically safe circuits, wiring diagrams for analog, RS485 and switch outputs, installation precautions and communication settings. It also explains the intrinsically safe parameters (Ui, Ii, Pi, Ci, Li, Uo, Io, Po, Co, Lo) and cable capacitance and inductance limits for the connecting cable. This manual is written in Chinese.

What's inside

  • Product introduction
  • Display panel and structure diagram
  • Model selection table
  • Technical parameters
  • Certification parameters
  • Matching principles
  • Wiring diagrams
  • Installation precautions
  • Communication settings

Specifications

Power supplyDC 24 V ±10%
Power consumptionRS485 output ≤0.7 W; analog output ≤1.4 W (single), ≤1.8 W (dual); switch output ≤1.4 W
Input signal types0–10 mA, 4–20 mA, 0–20 mA, 0–10 mA square root, 4–20 mA square root
Output signal typesAnalog output, RS485 signal output, switch output
Output loadCurrent output: RL ≤500 Ω; voltage output: RL ≥250 kΩ
Transmission delay / rateDelay ≤10 μs, signal transmission rate ≤9.6 kbps
Insulation strength1500 Vrms between intrinsically safe and non-intrinsically safe side (1 min, no spark)
Operating temperature-10 to 50 °C (no condensation, no freezing)
Storage temperature-10 to 60 °C (no condensation, no freezing)
Relative humidity25% to 85% RH
Explosion-proof marking【Exia Ga】IIC
CCC certificate number2021312316000086
Certification standardGB/T 3836.1-2021, GB/T 3836.4-2021
Maximum allowable voltage (terminals 7, 8, 10, 11)Um = 250 VAC/DC
CommunicationSerial RS485, baud rate 2400–9600 bps, one start bit, eight data bits, one stop bit

Frequently asked questions

What power supply does the NHR-A31 safety barrier need?

It requires an independent supply of DC 24 V ±10%, with three-way isolation between input, output and power.

What is the explosion-proof marking and certificate of the NHR-A31?

The marking is 【Exia Ga】IIC, certified to GB/T 3836.1-2021 and GB/T 3836.4-2021 with CCC certificate number 2021312316000086.

What communication settings does the meter support?

Serial RS485 with a baud rate of 2400 to 9600 bps, one start bit, eight data bits and one stop bit.

How is the safety barrier mounted?

It is mounted on a 35 mm DIN rail; the mounting position should be as vertical as possible so internal heat can dissipate.

Download PDF (836 KB)