Hong Run OHR-ES40 Series AC/DC Voltage/Current Over-Limit Alarm Instruction Manual

OHR-ES40 series AC/DC voltage/current over-limit alarm adopts new electromagnetic isolation principle to measure AC/DC voltage or current signals in the power grid and circuit in real time, with relay alarm output function; measurement and control integration, small size, high accuracy, fast response; with transient interference suppression function to prevent false operation. This product adopts standard 35mm DIN rail mounting, terminal wiring, easy installation and is suitable for various online voltage and current protection systems.


Hong Run OHR-ES40 Series AC/DC Voltage/Current Over-Limit Alarm Instruction Manual - cover page
Brand
Hong Run
Category
Monitoring Equipment
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
608 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
C620264160DE8C98264A193B1F08627F

About this manual

Hong Run OHR-ES40 series AC/DC voltage/current over-limit alarms measure AC or DC voltage or current using electromagnetic isolation and provide relay alarm output. The manual covers product introduction, dimensions, technical parameters, selection tables, wiring, application examples, threshold adjustment, and precautions.

The series includes ES41 AC voltage/current and ES42 DC voltage/current variants. It is DIN-rail mounted, uses DC24V power, and the alarm threshold is adjustable from 10% to 100% of the input range. This manual is written in Chinese.

What's inside

  • Structure Dimension Drawings
  • Technical Parameters
  • Selection Table
  • Wiring Diagram
  • Application Example
  • Alarm Threshold Adjustment
  • Precautions

Specifications

Input signalsWired: DC current 1mA/0.1A/1A/2A/5A and AC/DC voltage 10V/100V/500V/1000V; through-hole Φ8 AC current 1A/5A/10A/20A/50A; Φ20 AC current 30A/50A/80A/100A/200A/400A
Frequency band20 Hz to 5 kHz
OutputNormally open/normally closed relay contacts, AC240V/0.3A or DC30V/1A
Power supplyDC24V (±10%)
Isolation voltage1500 Vrms for 1 minute
Overload capabilityThrough-hole input: 30 times nominal input for 5 seconds; wired input: 10 times nominal input for 5 seconds
Operating temperature-10°C to 70°C
Relative humidity25% to 85% RH
Storage temperature-25°C to 85°C
Mounting35 mm DIN rail

Frequently asked questions

What power supply does the OHR-ES40 alarm require?

It operates from DC24V (±10%).

How is the alarm mounted?

It mounts on a 35 mm DIN rail.

How is the alarm threshold adjusted?

Connect DC24V power, adjust the alarm-value potentiometer, calculate VH, and set VH with a multimeter.