OHR-ES40 series AC/DC voltage/current over-limit alarm adopts new electromagnetic isolation principle to measure AC/DC voltage or current signals in the power grid and circuit in real time, with relay alarm output function; measurement and control integration, small size, high accuracy, fast response; with transient interference suppression function to prevent false operation. This product adopts standard 35mm DIN rail mounting, terminal wiring, easy installation and is suitable for various online voltage and current protection systems.
Hong Run OHR-ES40 series AC/DC voltage/current over-limit alarms measure AC or DC voltage or current using electromagnetic isolation and provide relay alarm output. The manual covers product introduction, dimensions, technical parameters, selection tables, wiring, application examples, threshold adjustment, and precautions.
The series includes ES41 AC voltage/current and ES42 DC voltage/current variants. It is DIN-rail mounted, uses DC24V power, and the alarm threshold is adjustable from 10% to 100% of the input range. This manual is written in Chinese.
| Input signals | Wired: DC current 1mA/0.1A/1A/2A/5A and AC/DC voltage 10V/100V/500V/1000V; through-hole Φ8 AC current 1A/5A/10A/20A/50A; Φ20 AC current 30A/50A/80A/100A/200A/400A |
|---|---|
| Frequency band | 20 Hz to 5 kHz |
| Output | Normally open/normally closed relay contacts, AC240V/0.3A or DC30V/1A |
| Power supply | DC24V (±10%) |
| Isolation voltage | 1500 Vrms for 1 minute |
| Overload capability | Through-hole input: 30 times nominal input for 5 seconds; wired input: 10 times nominal input for 5 seconds |
| Operating temperature | -10°C to 70°C |
| Relative humidity | 25% to 85% RH |
| Storage temperature | -25°C to 85°C |
| Mounting | 35 mm DIN rail |
It operates from DC24V (±10%).
It mounts on a 35 mm DIN rail.
Connect DC24V power, adjust the alarm-value potentiometer, calculate VH, and set VH with a multimeter.