Key facts
- Brand
- Hong Run
- Model
- NHR-A31
- Category
- Other
- Industry
- Industrial
- Documents
- 2
- Languages
- ZH
- Last added
- 2026-11-09
Start here

Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual
The NHR-A31 series current input isolated safety barrier converts current signals from the hazardous area into voltage, current, RS485 or switch signals and transmits them in isolation to the safe area. The unit requires an independent power supply and provides three-way isolation between input, output and power. It is tested to GB/T 3836.1-2021 and GB/T 3836.4-2021, holds a CCC certificate and can be used with intrinsically safe equipment in Zone 0, 1 and 2 hazardous gas areas. It mounts on a 35 mm DIN rail and has a working indicator that is green during normal operation and red for a fault signal.
This Chinese-language user manual covers the product introduction, panel and structure diagram, model selection table, technical parameters, certification parameters, matching principles for intrinsically safe circuits, wiring diagrams for analog, RS485 and switch outputs, installation precautions and communication settings. It also explains the intrinsically safe parameters (Ui, Ii, Pi, Ci, Li, Uo, Io, Po, Co, Lo) and cable capacitance and inductance limits for the connecting cable. This manual is written in Chinese.
Hongrun NHR-A31 specifications
| Power supply | DC 24 V ±10% |
|---|---|
| Power consumption | RS485 output ≤0.7 W; analog output ≤1.4 W (single), ≤1.8 W (dual); switch output ≤1.4 W |
| Input signal types | 0–10 mA, 4–20 mA, 0–20 mA, 0–10 mA square root, 4–20 mA square root |
| Output signal types | Analog output, RS485 signal output, switch output |
| Output load | Current output: RL ≤500 Ω; voltage output: RL ≥250 kΩ |
| Transmission delay / rate | Delay ≤10 μs, signal transmission rate ≤9.6 kbps |
| Insulation strength | 1500 Vrms between intrinsically safe and non-intrinsically safe side (1 min, no spark) |
| Operating temperature | -10 to 50 °C (no condensation, no freezing) |
| Storage temperature | -10 to 60 °C (no condensation, no freezing) |
| Relative humidity | 25% to 85% RH |
| Explosion-proof marking | 【Exia Ga】IIC |
| CCC certificate number | 2021312316000086 |
| Certification standard | GB/T 3836.1-2021, GB/T 3836.4-2021 |
| Maximum allowable voltage (terminals 7, 8, 10, 11) | Um = 250 VAC/DC |
| Communication | Serial RS485, baud rate 2400–9600 bps, one start bit, eight data bits, one stop bit |
Source: Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual
All Hongrun NHR-A31 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What power supply does the NHR-A31 safety barrier need?
It requires an independent supply of DC 24 V ±10%, with three-way isolation between input, output and power.
From: Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual
What is the explosion-proof marking and certificate of the NHR-A31?
The marking is 【Exia Ga】IIC, certified to GB/T 3836.1-2021 and GB/T 3836.4-2021 with CCC certificate number 2021312316000086.
From: Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual
What is the maximum input voltage for this device?
The maximum allowable voltage on the hazardous side (Um) is 250VAC/DC.
From: Hong Run NHR-A31 Series Voltage Input Isolation Barrier User Manual
What are the output power limits for analog and switch signals?
Analog outputs have a limit of ≤1.4W (single channel) or ≤1.8W (dual channels), while switch quantity outputs are limited to ≤1.4W.
From: Hong Run NHR-A31 Series Voltage Input Isolation Barrier User Manual