Hongrun NHR-A31 Manuals

ManualLib has 2 documents for the Hongrun NHR-A31 (Other): 2 user manuals. Every file can be read online or downloaded as a PDF for free.

User Manual 2

Key facts

Model
NHR-A31
Category
Other
Industry
Industrial
Documents
2
Languages
ZH
Last added
2026-11-09

Start here

Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual

Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual

User Manual 4 pages · 836 KB · ZH

The NHR-A31 series current input isolated safety barrier converts current signals from the hazardous area into voltage, current, RS485 or switch signals and transmits them in isolation to the safe area. The unit requires an independent power supply and provides three-way isolation between input, output and power. It is tested to GB/T 3836.1-2021 and GB/T 3836.4-2021, holds a CCC certificate and can be used with intrinsically safe equipment in Zone 0, 1 and 2 hazardous gas areas. It mounts on a 35 mm DIN rail and has a working indicator that is green during normal operation and red for a fault signal.

This Chinese-language user manual covers the product introduction, panel and structure diagram, model selection table, technical parameters, certification parameters, matching principles for intrinsically safe circuits, wiring diagrams for analog, RS485 and switch outputs, installation precautions and communication settings. It also explains the intrinsically safe parameters (Ui, Ii, Pi, Ci, Li, Uo, Io, Po, Co, Lo) and cable capacitance and inductance limits for the connecting cable. This manual is written in Chinese.

Read online

Hongrun NHR-A31 specifications

Power supplyDC 24 V ±10%
Power consumptionRS485 output ≤0.7 W; analog output ≤1.4 W (single), ≤1.8 W (dual); switch output ≤1.4 W
Input signal types0–10 mA, 4–20 mA, 0–20 mA, 0–10 mA square root, 4–20 mA square root
Output signal typesAnalog output, RS485 signal output, switch output
Output loadCurrent output: RL ≤500 Ω; voltage output: RL ≥250 kΩ
Transmission delay / rateDelay ≤10 μs, signal transmission rate ≤9.6 kbps
Insulation strength1500 Vrms between intrinsically safe and non-intrinsically safe side (1 min, no spark)
Operating temperature-10 to 50 °C (no condensation, no freezing)
Storage temperature-10 to 60 °C (no condensation, no freezing)
Relative humidity25% to 85% RH
Explosion-proof marking【Exia Ga】IIC
CCC certificate number2021312316000086
Certification standardGB/T 3836.1-2021, GB/T 3836.4-2021
Maximum allowable voltage (terminals 7, 8, 10, 11)Um = 250 VAC/DC
CommunicationSerial RS485, baud rate 2400–9600 bps, one start bit, eight data bits, one stop bit

Source: Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual

All Hongrun NHR-A31 documents by type

User Manual 2

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What power supply does the NHR-A31 safety barrier need?

It requires an independent supply of DC 24 V ±10%, with three-way isolation between input, output and power.

From: Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual

What is the explosion-proof marking and certificate of the NHR-A31?

The marking is 【Exia Ga】IIC, certified to GB/T 3836.1-2021 and GB/T 3836.4-2021 with CCC certificate number 2021312316000086.

From: Hongrun NHR-A31 Series Current Input Isolated Safety Barrier User Manual

What is the maximum input voltage for this device?

The maximum allowable voltage on the hazardous side (Um) is 250VAC/DC.

From: Hong Run NHR-A31 Series Voltage Input Isolation Barrier User Manual

What are the output power limits for analog and switch signals?

Analog outputs have a limit of ≤1.4W (single channel) or ≤1.8W (dual channels), while switch quantity outputs are limited to ≤1.4W.

From: Hong Run NHR-A31 Series Voltage Input Isolation Barrier User Manual