Installation, operation and maintenance manual for Grundfos IMpress Basic, Advanced, Glycol and H/C pressurization sets.
The manual covers Grundfos IMpress pressurization sets in Basic, Advanced, Glycol and H/C versions. It is written as a guide to installation, putting into service, operation and maintenance, and states that it does not contain full service instructions.
It covers delivery and handling, warranty, site storage, applications for sealed heating and chilled water systems, maximum operating conditions, installation location and foundation, pressure vessel requirements, cabinet cover removal, pipework and electrical connections, dimensions and connection details, and pressure display change.
| Liquid temperature range | 3 to +90 °C |
|---|---|
| Ambient temperature | +40 °C maximum |
| Relative humidity | up to 95 % |
| Maximum operating pressure | 6 Bar |
| Recommended maximum start-stops per hour | 20-30 |
| Water supply connection | ½" BSP male |
| Overflow pipe | ¾" BSP male |
| System connection | 15 mm compression |
| Electrical supply | 240 V single phase, 13 A |
They are designed for pressurization of sealed heating systems and sealed chilled water systems.
The maximum operating pressure is 6 Bar.
The warranty covers defects for one year from installation or eighteen months from factory despatch, whichever is sooner.
Inspect the unit for signs of damage before signing the delivery note and report any damage to the supplier within 7 days.