Autonics THD Series Temperature/Humidity Transducer User Manual

This manual covers the Autonics THD series temperature and humidity transducers, including specifications, installation, wiring diagrams, and Modbus RTU…


Autonics THD Series Temperature/Humidity Transducer User Manual - cover page
Brand
Autonics
Category
Other Electronics
Document type
User Manual
Language
English
Pages
7
File format
PDF
File size
497 KB
Published
20 October, 2026
Updated
20 October, 2026
MD5 checksum
DA82051D83A149490F720C95A695038C

About this manual

The document provides a comprehensive overview of the Autonics THD Series Temperature/Humidity Transducer. It details various models (THD-R-PT through THD-WD) with different mounting types (Room, Duct, Wall), sensor lengths, and output modes including DC 4-20mA, 1-5VDC, and RS485 Modbus RTU communication.

What's inside

  • Specifications
  • Features
  • Mounting Types
  • Terminal Connections
  • Voltage Output Functions
  • Current Output Functions
  • RS485 Communication Protocol
  • Modbus RTU Data Format

Specifications

Power supply24VDC (Allowable range: 90 to 110% of rated voltage)
Measuring inputTemperature (Built-in sensor), Humidity (Built-in sensor)
Measurement range (Temp.)-19.9 to 60.0 ℃
Measurement range (Humidity)0.0 to 99.9%RH
Accuracy (Temp.)Max. ±0.8 ℃ +1.0℃ (at room temperature)
Communication speed1200 to 115200bps

Frequently asked questions

What is the allowable impedance for current output?

The allowable impedance of current output is max. 600Ω.

How do you calculate the current temperature value from Modbus data?

Divide the read 16-bit value by 100 (e.g., 2480 / 100 = 24.80 ℃).

What is the maximum communication distance for RS485?

The effective communication distance is max. 800m.