The Armstrong The Brain DMC80-80-80BS is a Digital Mixing Center designed to be the primary water temperature controller in a recirculating hot water system. It features three digital recirculation valves (The Brain) piped in parallel and is supplied as a complete pre-piped assembly with isolation valves, check valves, strainers, thermometers, and pressure gauges.

The document provides pressure-drop performance charts and technical specifications for protection, ambient conditions, materials, connections, pressures, temperatures, electrical power, battery, configurable settings, connectivity, and standards and approvals. It also includes written specifications, SAGE options, and warranty terms.

What's inside

  • Performance Chart
  • Technical Specifications
  • Written Specifications
  • Connectivity
  • SAGE® Options
  • Optional Building System (BS) Module
  • The Brain® and SAGE®
  • Standards and Approvals

Specifications

ProtectionNEMA 3S, IPX4
Ambient Temperature35°F to 122°F (2°C to 50°C)
MaterialsValve: Stainless Steel; Electronics Module: PC / ABS
DRV Connections3” NPT
Hot & Cold Water Inlet Connections5” Flange ANSI 150
Maximum Pressure (DRV)200 psi / 1379 kPA = 13.8 bar
Maximum Inlet Hot Supply Temperature185°F (85°C)
Minimum Recirculation Temperature Loss1°F ( < 1°C)
Minimum Continuous Recirculation Flow10 GPM (38 LPM) per DRV80 valve (30 GPM / 114 LPM total)
Power Supply120 - 240V AC - 50/60 Hz
Set Point Range81°F to 158°F (27°C to 70°C)
Thermal Disinfection Temperature158°F to 185°F (70°C to 85°C)
ConnectivityModbus RTU RS-485 port; RS-485 port for SAGE module
Standards and ApprovalsASSE 1017 Certified & Listed; CSA B125.3-11 Compliant; UL Listed; CE Listed
Warranty5-year warranty on all components, except batteries and O-rings

Frequently asked questions

What is the DMC80-80-80BS used for?

It is designed to be the primary water temperature controller in a recirculating hot water system.

How many digital recirculation valves does the DMC80-80-80BS have?

It has three digital recirculation valves (The Brain) piped in parallel.

What is the set point range?

The set point range is 81°F to 158°F (27°C to 70°C).

What standards and approvals does the DMC80-80-80BS have?

It is ASSE 1017 Certified & Listed, CSA B125.3-11 Compliant, UL Listed, and CE Listed.