Guide specifications for the APC Smart-UPS RT 2400VA and 3000VA static uninterruptible power supply systems, covering mechanical design, system…
This document provides guide specifications for the APC Smart-UPS RT series, available in Tower or Rack-Mount configurations. The units utilize a double conversion online topology to provide network-grade power with tight voltage and frequency regulation, featuring internal bypass and input power factor correction.
Key system characteristics include a minimum efficiency of 91%, an input power factor of at least 0.95 lagging, and the ability to support loads up to 2400VA (1680W) or 3000VA (2100W). The UPS operates in Online, On Battery, Bypass, and External Service Bypass Panel modes to ensure continuous power for mission-critical equipment.
| System Capacity (2400VA Model) | 2400VA or 1680W whichever limit is reached first |
|---|---|
| System Capacity (3000VA Model) | 3000VA or 2100W whichever limit is reached first |
| Efficiency | at least 91% |
| Input Nominal Voltage (120VAC models) | 120VAC |
| Input Nominal Voltage (100VAC models) | 100VAC |
| Output Connectors (2400VA models) | 3 NEMA 5-15R; 2 NEMA 5-20R; 1 NEMA L5-20R |
| Output Connectors (3000VA models) | 6 NEMA 5-15R; 2 NEMA 5-20R |
| Operating Ambient Temperature | +32 °F to 104 °F (0°C to 40°C) |
Yes, the UPS batteries are modular, hot-swappable, and user-replaceable.
The input power factor is a minimum of 0.95 lagging at 100% load at nominal voltage.