ABB 9438 Dissolved Oxygen Monitor User Manual covers installation, electrical connection, operation, calibration, and maintenance of the 9438 dissolved…
This user manual covers the ABB 9438 low-concentration dissolved oxygen monitoring system, including the 9438 500 wall-mounted transmitter and the 9438 501 panel-mounted 1/4 DIN instrument. It describes mechanical installation, electrical connections, assembly, startup, operation, programming, electrical calibration, maintenance, and troubleshooting.
The transmitter and flow cell continuously monitor and control power plant boiler feedwater and steam condensate. The instrument has one programmable DO input channel and one temperature input channel, with temperature sensed by a Pt1000 resistance thermometer in the flow cell. Operation and programming use four touch membrane switches on the front panel, protected by a five-digit security code. This manual is written in Chinese.
| Sample flow rate | 100 to 400 ml/min |
|---|---|
| Cable diameter | 4 to 7 mm |
| Minimum relay voltage | greater than 12 V |
| Minimum relay current | greater than 100 mA |
The dissolved oxygen transmitter and flow cell are designed to continuously monitor and control power plant boiler feedwater and steam condensate.
Operation and programming are performed using four touch membrane switches on the front panel, with programs protected by a five-digit security code.
The 9438 500 is a wall-mounted transmitter, and the 9438 501 is a panel-mounted 1/4 DIN instrument.
The sample flow rate must be between 100 and 400 ml/min.