Honeywell 236 Plus Control Host Installation Guide

236 Plus control host installation manual, introduces the installation, wiring, start-up, keyboard setting, programming and other content of the host.


Brand
Honeywell
Document type
Installation Guide
Language
Chinese
Pages
36
File format
PDF
File size
715 KB
Updated
01 October, 2023
MD5 checksum
A75A7AF495153427396C7C6140243CA8

About this manual

This manual provides step‑by‑step instructions for installing the Honeywell 236 Plus control host. It includes wiring diagrams, power‑supply requirements, grounding, and recommended settings for fire and intrusion zones.

The guide also details programming using LED or LCD keyboards, external relay connections, battery replacement procedures, and troubleshooting of common issues such as power loss or loop faults. This manual is written in Chinese.

What's inside

  • Installation Overview
  • Wiring Diagram
  • Recommended Settings
  • Keyboard Programming
  • Power Supply Requirements
  • External Relay Connections
  • Loop Configuration
  • Battery Maintenance

Specifications

Battery type12 VDC sealed lead‑acid, 6.5 Ah (model 1265) or 4.0 Ah (model 1240)
BELL port current800 mA at 9.5‑14.0 VDC
AUX and KEY+ total current limit400 mA
Transformer specification16.5 VAC, 25‑40 VA, 50/60 Hz, UL listed category 2
Loop voltage thresholds0.00‑1.50 VDC short, 1.60‑3.10 VDC normal, 3.20‑5.00 VDC open

Frequently asked questions

How often should the battery be replaced?

Replace the sealed lead‑acid battery every 3 to 5 years.

What is the maximum current allowed on the BELL port?

The BELL port can supply up to 800 mA at 9.5‑14.0 VDC.

What type of transformer is required for the control host?

A 16.5 VAC, 25‑40 VA transformer rated for 50/60 Hz and UL category 2 is required.

What are the voltage ranges that indicate loop status?

0.00‑1.50 VDC indicates a short, 1.60‑3.10 VDC normal operation, and 3.20‑5.00 VDC an open circuit.

Download PDF (715 KB)