This document is a site preparation guide for the 40U-P cabinet. It contains information on environmental requirements, shock and vibration, cabinet clearance, cabinet stabilizing, site floor load-bearing requirements, casters and leveling feet, power requirements, package dimensions and clearances, and what to do next.
This Site Preparation Guide contains information about the Dell EMC 40U-P cabinet, including environmental requirements such as temperature, humidity, and air quality. It also details shock and vibration tolerances and necessary cabinet clearances for service and cooling.
| Operating Temperature | +15°C to +32°C (59°F to 89.6°F) |
|---|---|
| Relative Humidity | 40% to 55% |
| Operating Altitude | 0 to 2439 meters (0 to 8,000 feet) |
| Empty Cabinet Weight | 198 KG (435 lbs) |
| Maximum Floor Load per Cabinet | 1,180kg (2,600 lbs.) |
| Floor Tile Concentrated Load Rating | 1,000 lb (454 kg) |
| Floor Tile Static Ultimate Load | 3,000 lb (1,361 kg) |
| Non operational shock tolerance | 10 G's, 7 ms duration |
The recommended site temperature is +15°C to +32°C (59°F to 89.6°F).
The data center should maintain a cleanliness level as identified in ISO 14664-1, class 8 for particulate dust and pollution control.
24 x 24 inch or (60 x 60 cm) heavy-duty, concrete filled steel floor tiles are recommended.
The floor must be capable of supporting at least 1,180kg (2,600 lbs.) per cabinet.