Danfoss VLT® Drives Safe Torque Off (STO) Function Guide

The Danfoss VLT® Drives Safe Torque Off (STO) Function Guide provides information on how to use Danfoss VLT® drives in safety function applications.


Danfoss VLT® Drives Safe Torque Off (STO) Function Guide - cover page
Brand
Danfoss
Category
Industrial Supply
Document type
User Manual
Language
Spanish
Pages
19
File format
PDF
File size
1.2 MB
Published
18 November, 2023
Updated
18 November, 2023
MD5 checksum
226ABFD8A79C0843F84626BFFDA24CC1

About this manual

This guide explains the Safe Torque Off (STO) function for Danfoss VLT frequency converters and its use in functional safety applications. It covers safety requirements, installation, commissioning, system configuration security, service and maintenance, and STO technical data.

The STO function is available for selected VLT drive models, including HVAC Drive FC 102, Refrigeration Drive FC 103, AQUA Drive FC 202, AutomationDrive FC 301 size A1, AutomationDrive FC 302, Decentral Drive FCD 302, and Parallel Drive Modules. Configuration is identified through the unit's descriptive code on the nameplate. This manual is written in Spanish.

What's inside

  • Introduction
  • Safety
  • Installation
  • Commissioning
  • STO technical data
  • Index

Specifications

Stop categoryCategory 0 (EN 60204-1)
Safety categoryCategory 3 (EN ISO 13849-1)
Performance levelPL d (EN ISO 13849-1)
Safety integrity levelSIL 2 (IEC/EN 61508, EN 61800-5-2)
SIL claim limitSILCL 2 (EN 62061)
STO control terminalTerminal 37

Frequently asked questions

Which Danfoss VLT drives include the STO function?

The guide lists VLT HVAC Drive FC 102, Refrigeration Drive FC 103, AQUA Drive FC 202, AutomationDrive FC 301 size A1, AutomationDrive FC 302, Decentral Drive FCD 302, and Parallel Drive Modules.

How can I confirm that a drive is configured with STO?

Check the unit's descriptive code on the nameplate; the required digit 18 value depends on the drive model.

What safety ratings does the integrated STO function meet?

It meets Category 3 and performance level d under EN ISO 13849-1, SIL 2 under IEC/EN 61508 and EN 61800-5-2, and SILCL 2 under EN 62061.

Which control terminal provides STO?

STO is provided through control terminal 37.