The Danfoss VLT® Drives Safe Torque Off (STO) Function Guide provides information on how to use Danfoss VLT® drives in safety function applications.
This guide explains the Safe Torque Off (STO) function for Danfoss VLT frequency converters and its use in functional safety applications. It covers safety requirements, installation, commissioning, system configuration security, service and maintenance, and STO technical data.
The STO function is available for selected VLT drive models, including HVAC Drive FC 102, Refrigeration Drive FC 103, AQUA Drive FC 202, AutomationDrive FC 301 size A1, AutomationDrive FC 302, Decentral Drive FCD 302, and Parallel Drive Modules. Configuration is identified through the unit's descriptive code on the nameplate. This manual is written in Spanish.
| Stop category | Category 0 (EN 60204-1) |
|---|---|
| Safety category | Category 3 (EN ISO 13849-1) |
| Performance level | PL d (EN ISO 13849-1) |
| Safety integrity level | SIL 2 (IEC/EN 61508, EN 61800-5-2) |
| SIL claim limit | SILCL 2 (EN 62061) |
| STO control terminal | Terminal 37 |
The guide lists VLT HVAC Drive FC 102, Refrigeration Drive FC 103, AQUA Drive FC 202, AutomationDrive FC 301 size A1, AutomationDrive FC 302, Decentral Drive FCD 302, and Parallel Drive Modules.
Check the unit's descriptive code on the nameplate; the required digit 18 value depends on the drive model.
It meets Category 3 and performance level d under EN ISO 13849-1, SIL 2 under IEC/EN 61508 and EN 61800-5-2, and SILCL 2 under EN 62061.
STO is provided through control terminal 37.