Woodward MRA1 Trip Circuit Supervision Relay Manual

The MRA1 relay is used to monitor the tripping circuit of protection devices, taking into account the following factors:


Woodward MRA1 Trip Circuit Supervision Relay Manual - cover page
Brand
Woodward
Category
electric relay
Document type
User Manual
Language
English
Pages
20
File format
PDF
File size
301 KB
Published
17 November, 2023
Updated
17 November, 2023
MD5 checksum
000E2E095561D6FC25CF07D1CC2C7294

About this manual

The Woodward MRA1 is a trip circuit supervision relay used to supervise the tripping circuit of protective devices, including auxiliary voltage, cable break and mechanical functions of the circuit breaker. It provides manual or automatic reset and supports trip coil resistances up to 12 kΩ.

The manual covers connections, coding plugs for input thresholds and LED function, front-panel indicators, testing and commissioning, and technical data such as supply voltage, output contacts, breaking capacity and ambient temperature limits.

What's inside

  • Introduction and application
  • Features and characteristics
  • Design and connections
  • Coding plug
  • Coding of the LED function
  • Coding Auto/Manual Reset
  • Functions
  • Front plate
  • Testing and commissioning
  • Technical Data

Specifications

Supply voltage16–360 V DC / 16–270 V AC
Output contacts4 change-over contacts
Breaking capacity (AC)2000 VA / max. 250 V
Breaking capacity (DC, ohmic)30 V / 8 A; 110 V / 0.5 A; 300 V / 0.3 A
Power consumptionmax. 9.2 W at 24 V; max. 9.4 W at 110 V; max. 9.8 W at 220 V
Reset time<100 ms
Tripping time (switching failure)>400 ms
Tripping time (supply voltage failure)>200 ms
Trip coil resistance0–12 kΩ
Ambient service temperature (operation)-10°C to +55°C
Storage temperature-25°C to +70°C
Degree of protectionIP 54

Frequently asked questions

What does the MRA1 supervise?

It supervises the tripping circuit of protective devices, including auxiliary voltage, cable break and mechanical functions of the circuit breaker.

When does automatic reset occur?

Automatic reset occurs when the coding plug is plugged in and the fault has been corrected.

How is manual reset performed?

Manual reset is performed by activating the reset key or the external reset function.

What input switching thresholds are available?

Four switching thresholds are available: 9 V, 30 V, 65 V and 100 V.