The MRA1 relay is used to monitor the tripping circuit of protection devices, taking into account the following factors:
The Woodward MRA1 is a trip circuit supervision relay used to supervise the tripping circuit of protective devices, including auxiliary voltage, cable break and mechanical functions of the circuit breaker. It provides manual or automatic reset and supports trip coil resistances up to 12 kΩ.
The manual covers connections, coding plugs for input thresholds and LED function, front-panel indicators, testing and commissioning, and technical data such as supply voltage, output contacts, breaking capacity and ambient temperature limits.
| Supply voltage | 16–360 V DC / 16–270 V AC |
|---|---|
| Output contacts | 4 change-over contacts |
| Breaking capacity (AC) | 2000 VA / max. 250 V |
| Breaking capacity (DC, ohmic) | 30 V / 8 A; 110 V / 0.5 A; 300 V / 0.3 A |
| Power consumption | max. 9.2 W at 24 V; max. 9.4 W at 110 V; max. 9.8 W at 220 V |
| Reset time | <100 ms |
| Tripping time (switching failure) | >400 ms |
| Tripping time (supply voltage failure) | >200 ms |
| Trip coil resistance | 0–12 kΩ |
| Ambient service temperature (operation) | -10°C to +55°C |
| Storage temperature | -25°C to +70°C |
| Degree of protection | IP 54 |
It supervises the tripping circuit of protective devices, including auxiliary voltage, cable break and mechanical functions of the circuit breaker.
Automatic reset occurs when the coding plug is plugged in and the fault has been corrected.
Manual reset is performed by activating the reset key or the external reset function.
Four switching thresholds are available: 9 V, 30 V, 65 V and 100 V.