The system configuration when connecting Azbil Corporation's remote controller to the HMI is shown in the table below.
This manual explains how to connect a Pro-face GP-Pro EX human-machine interface to Azbil Corporation external controllers (target PLCs) using the MODBUS TCP Master driver. It covers system configuration, selecting the external controller, communication setup examples, and setting items in GP-Pro EX or offline mode.
It also lists supported registers and address codes, and describes error messages, including controller-specific error codes and their meanings. This manual is written in Chinese.
| Connected external controllers | 1 to 4; expandable to 64 when enabled |
|---|---|
| Allowed controllers/PLCs when expanded | 64 |
| HMI port number range | 1024 to 65535 |
| Timeout range | 1 to 127 seconds |
| Retry count range | 0 to 255 |
| Wait to send range | 0 to 5000 ms |
| External controller default IP address | 192.168.255.254 |
Enter an integer from 1 to 4; if 'Increase allowed number of controllers/PLCs' is checked, the allowed number can be expanded to 64.
The default IP address is 192.168.255.254.
Error code 06 means the external controller is busy.
A read error may not be displayed, the read data remains 0, and a write error is displayed.