Acrel AMI-250 Single-Phase Grid-Connected Photovoltaic Microinverter Installation and User Manual

AMI-250 single-phase grid-connected photovoltaic microinverter installation and user manual


Acrel AMI-250 Single-Phase Grid-Connected Photovoltaic Microinverter Installation and User Manual - cover page
Brand
Acrel
Category
inverter
Document type
User Manual
Language
Chinese
Pages
13
File format
PDF
File size
1.5 MB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
836CF1E354E645D57758666BAA8A1297

About this manual

This manual describes the Acrel AMI-250 single-phase grid-connected photovoltaic microinverter, which uses DSP control, has one DC input, performs MPPT control, and communicates via power-line carrier technology.

It provides technical parameters, dimensions, required tools, safety and installation notes, installation and replacement steps, operating status, maintenance and troubleshooting guidance, and single-phase and three-phase wiring diagrams. This manual is written in Chinese.

What's inside

  • System Introduction
  • Technical Parameters
  • Appearance and Installation Dimensions
  • Tools Required for Installation
  • Safety Information and Installation Notes
  • Installation Steps
  • Microinverter Replacement
  • Operating Status
  • Maintenance and Troubleshooting
  • Output Reference Wiring Diagrams

Specifications

Maximum operating voltage (PV side)50 V
Maximum withstand voltage (PV side)56 V
MPPT voltage range28-45 V
Input startup voltage28 V
Input shutdown voltage20 V
Maximum input current10 A
MPPT efficiency>99%
Maximum input power250 W
Operating voltage range (AC side)210-265 V
Maximum withstand voltage (AC side)270 V
Operating frequency range49.5-50.5 Hz
Normal output current1 A
Maximum output current1.2 A
AC power235 W
Power factor>0.99
Output current THD<5%
Maximum efficiency94.5%
Nighttime self-consumption<0.25 W
Operating ambient temperature-40 to +65 C
Storage temperature-40 to +80 C
Protection ratingIP65
Dimensions260*160*40
Cooling methodNatural cooling without fan

Frequently asked questions

How many AMI-250 microinverters can be connected on one branch?

No more than 16 microinverters can be connected on one branch.

What spacing is required between the microinverter and the PV panel?

The microinverter and PV panel must be separated by at least 2 cm.

How long after closing the breakers does the system start generating power?

The system starts generating power 3 minutes after the breakers are closed.

What does the indicator light show during normal startup?

When DC power is applied, the indicator light turns red and then flashes green, indicating normal startup.

Download PDF (1.5 MB)