Acrel 316 A-D-0.5KVA-A200 Emergency Lighting Central Power Supply Installation and Use Manual

Installation and use manual for the Acrel 316 A-D-0.5KVA-A200 emergency lighting central power supply, covering specifications, wiring, and maintenance.


Acrel 316 A-D-0.5KVA-A200 Emergency Lighting Central Power Supply Installation and Use Manual - cover page
Brand
Acrel
Document type
User Manual
Language
Chinese
Pages
6
File format
PDF
File size
297 KB
Published
13 October, 2026
Updated
13 October, 2026
MD5 checksum
DB109D44988FBE9164AFF54A6BBCB867

About this manual

This document is the installation and user guide for the Acrel 316 A-D-0.5KVA-A200 Emergency Lighting Central Power Supply. The device serves as a backup centralized power source installed within buildings to supply fire emergency lighting and evacuation indicator signs, ensuring their normal operation during emergencies. This manual is written in Chinese.

What's inside

  • Product Overview
  • Technical Parameters
  • Panel Component Layout
  • External Dimensions
  • Wiring and Installation
  • Precautions

Specifications

Input PowerAC220V (85%~110%) 50Hz
Output Power500W
Output VoltageDC36V
Backup Capacity12V/38Ah, 3 cells
Emergency Time90min
Switching Time≤5s
Communication BusUpward CAN bus
Supply Distance≤30m
Dimensions700*560*280 (H*W*D) mm
Operating Temperature-10℃~+55℃

Frequently asked questions

What is the recommended height for mounting the device?

The bottom edge of the device should be installed at a distance of 1.3m to 1.5m from the ground.

What type of cable is recommended for the CAN bus communication?

It is recommended to use NH-RVSP-2×1.5mm² shielded twisted pair cables.