Installation and usage manual for the Acrel ACTB series current transformer overvoltage protector, covering specifications, wiring, testing, and ordering.
This document is an installation and user guide for the Acrel ACTB series Current Transformer (CT) Overvoltage Protector. The device protects CT secondary circuits from dangerous open-circuit voltages caused by faults like lightning or resonance. It operates by detecting abnormal high voltage spikes, limiting them, and shorting the circuit to prevent damage to equipment and ensure safety. This manual is written in Chinese.
| Normal leakage current | <20uA |
|---|---|
| Input resistance | >100MΩ |
| Conduction voltage (default) | AC 150V(±10%) |
| Conduction time | 50ms≤Ts≤250ms |
| Action life | 1×105次 |
| Working environment temperature | -20℃~70℃ |
| Installation method | DIN35 导轨式 |
It can be reset by pressing the 'Reset' button or automatically upon power outage.
The communication relay supports AC220/5A and DC110V/5A, while the protection relay supports AC220V/15A.