Endress+Hauser Prosonic T FMU30 Ultrasonic Level Transmitter Brief Operating Guide

Prosonic T FMU30 is an ultrasonic level transmitter with the following features: - Wide measuring range up to 15 m - High accuracy of ±0.2% - Unaffected by environmental influences - Simple operation and maintenance


Endress+Hauser Prosonic T FMU30 Ultrasonic Level Transmitter Brief Operating Guide - cover page
Brand
Endress+Hauser
Category
sensor
Document type
User Manual
Language
Chinese
Pages
32
File format
PDF
File size
1.6 MB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
0183785BD6674CF286E3D0B9BA7F4E42

About this manual

This document is the Brief Operating Guide (简明操作指南) for the Endress+Hauser Prosonic T FMU30, a compact ultrasonic measuring device for continuous, non-contact level measurement of liquids and solids. The guide states it does not replace the Operating Manual supplied on the enclosed CD, and directs users to www.endress.com/deviceviewer for further documentation.

The text covers safety instructions, mounting methods and mounting conditions (including standoff pipe installation, blind zone distances and beam angle limits), electrical wiring and terminal assignment, the display and operating menu structure, and commissioning steps such as function check and basic setup. It also describes use for open-channel and weir flow measurement with linearization, with mounting examples for a Khafagi-Venturi flume and a triangular weir. This manual is written in Chinese.

What's inside

  • 安全指南 (Safety guidelines)
  • 安装 (Installation)
  • 安装条件 (Mounting conditions)
  • 测量范围 (Measuring range)
  • 接线 (Wiring)
  • 操作 (Operation)
  • 显示与操作单元 (Display and operating unit)
  • 调试 (Commissioning)
  • 基本设置 (Basic setup)

Specifications

Max measuring range (liquids)8 m (26 ft)
Max measuring range (solids)3.5 m (11 ft)
Beam angle11°
Blind zone distance0.25 m (0.8 ft) for 1½" sensor; 0.35 m (1.1 ft) for 2" sensor
Max range, 1½" sensor5 m (16 ft) liquids; 2 m (6.6 ft) solids
Storage temperature-40 °C to +80 °C (-40 °F to +176 °F)
Process connectionsG1½ and G2 threaded connections

Frequently asked questions

How far from the tank wall should the FMU30 sensor be mounted?

The recommended distance between the sensor and the tank wall is about 1/6 of the tank diameter, and the sensor should not be mounted in the center of the tank.

Can two ultrasonic measuring devices be installed on the same tank?

No, the guide states that two ultrasonic measuring devices must not be installed on the same tank because the two signals may interfere with each other.

Does this guide replace the Operating Manual?

No, the Brief Operating Guide does not replace the Operating Manual supplied with the device on CD; it refers users to the manual for detailed information.

What standoff pipe diameter is needed for guided measurement in narrow channels?

When using a guide pipe (e.g. PE or PVC wastewater pipe) in narrow channels with strong interference echoes, the minimum pipe diameter is 100 mm (3.94 in).

Download PDF (1.6 MB)