This manual describes how to use the CC-Link system small remote I/O module.
This is the detailed edition of the Mitsubishi Electric user manual for the CC-Link System small remote I/O modules (document number SH(NA)-080234C). It opens with safety precautions for design, installation, wiring, start-up and maintenance, followed by an overview chapter, a specifications list, general specifications and input module specifications. The revision record shows a first edition dated November 2001 and a fully revised second edition dated December 2006.
The manual explains how to read the model names of the small remote I/O modules, points to note when selecting them, separately sold parts and recommended products for connecting devices, and gives the names and settings of each part. The input module chapter covers AC 100V input modules such as AJ65SBTB2N-8A and AJ65SBTB2N-16A and DC 24V input modules with sink/source shared common, including AJ65SBTB1-16D and AJ65SBTB1-16D1. This manual is written in Chinese.
| Terminal screw tightening torque | 42 to 50 N·cm |
|---|---|
| Grounding | Type D grounding (third class grounding) or better |
| Ingress protection | IP67, achieved only when the waterproof plug, waterproof cap and communication connector are installed |
| AC 100V input module models | AJ65SBTB2N-8A, AJ65SBTB2N-16A |
| DC 24V input common type | Positive common (sink) and negative common (source) shared type |
All input points from the remote I/O station turn OFF and all output points from the remote I/O station turn OFF. The manual says interlocks should be configured in the sequence program so the whole system moves in a safe direction.
The terminal screws must be tightened within a torque range of 42 to 50 N·cm.
Use Type D grounding (third class grounding) or better, dedicated to the programmable controller.