GoodWe N-MT Series Photovoltaic Grid-Connected Inverter User Manual

GoodWe photovoltaic grid-connected inverter series products are strictly designed in accordance with relevant safety regulations. However, as electrical and electronic equipment, the following safety instructions must be observed during installation and maintenance. Improper operation will cause serious injury and property damage to the operator and third parties.


GoodWe N-MT Series Photovoltaic Grid-Connected Inverter User Manual - cover page
Brand
Goodwe
Category
inverter
Document type
User Manual
Language
Chinese
Pages
14
File format
PDF
File size
5.2 MB
Published
11 November, 2023
Updated
11 November, 2023
MD5 checksum
9779BAA819030A281E8F1E8C17580801

About this manual

This is the Chinese user manual for the GoodWe N-MT series photovoltaic grid-connected inverter, a three-phase unit covering the GW50KN-MT, GW60KN-MT and GW70KHV-MT models. It opens with symbol definitions and safety warnings, then describes the inverter layout, package contents and the mechanical and electrical installation steps, including AC and DC wiring, protective earthing, USB, RS485, WiFi and GPRS connections.

The second half of the manual explains operation: indicator light states for models with and without an LCD screen, display and key functions, fault codes and disclaimers, and how to restart the WiFi module or restore factory settings. It closes with an FAQ, technical parameters, a main circuit diagram, maintenance tasks such as fan cleaning, DC switch checks, electrical connection checks and fuse replacement, plus related certifications. This manual is written in Chinese.

What's inside

  • 符号释义 (Symbol Definitions)
  • 安全说明与警告 (Safety Instructions and Warnings)
  • 安装说明 (Installation Instructions)
  • 逆变器外观介绍与包装信息 (Appearance and Package Contents)
  • 设备安装 (Mechanical Installation)
  • 电气安装 (Electrical Installation)
  • 指示灯说明 (Indicator Light Description)
  • 显示屏和按键说明 (Display and Keypad)
  • 故障代码 (Fault Codes)
  • WiFi模块重启和恢复出厂设置 (WiFi Module Restart and Factory Reset)

Specifications

GW50KN-MT output current80 A
GW60KN-MT output current90 A
GW70KHV-MT output current89 A
Recommended AC circuit breaker (GW50KN-MT)100 A
AC cable cross-section25~95 mm² (50 mm² copper recommended)
Neutral-to-earth impedanceLess than 10 ohms
External leakage protection device trip current300 mA or higher
AC terminal tightening torque8~10 N·m
RS485 cable total lengthNot more than 1000 m
Maximum stacking layers of packaging6 layers
TT grid neutral-to-earth voltageBelow 20 V RMS

Frequently asked questions

How long must I wait after disconnecting power before touching the inverter?

At least 5 minutes must pass after disconnecting the AC grid and DC input, so that the machine is fully discharged.

Which utility grid types do the GW50KN-MT and GW60KN-MT support?

These three-phase models support TN-S, TN-C, TN-C-S and TT grid types; for TT grids the RMS voltage between neutral and earth must be below 20 V.

What is the maximum length of the RS485 communication cable?

The total length of the cable connecting the inverter to the EzLogger Pro must not exceed 1000 m, and the communication cable must be kept apart from power lines.

How many layers of packaging can be stacked?

The packaging can be stacked up to 6 layers maximum.