GoodWe photovoltaic grid-connected inverter series products are strictly designed in accordance with relevant safety regulations. However, as electrical and electronic equipment, the following safety instructions must be observed during installation and maintenance. Improper operation will cause serious injury and property damage to the operator and third parties.
This is the Chinese user manual for the GoodWe N-MT series photovoltaic grid-connected inverter, a three-phase unit covering the GW50KN-MT, GW60KN-MT and GW70KHV-MT models. It opens with symbol definitions and safety warnings, then describes the inverter layout, package contents and the mechanical and electrical installation steps, including AC and DC wiring, protective earthing, USB, RS485, WiFi and GPRS connections.
The second half of the manual explains operation: indicator light states for models with and without an LCD screen, display and key functions, fault codes and disclaimers, and how to restart the WiFi module or restore factory settings. It closes with an FAQ, technical parameters, a main circuit diagram, maintenance tasks such as fan cleaning, DC switch checks, electrical connection checks and fuse replacement, plus related certifications. This manual is written in Chinese.
| GW50KN-MT output current | 80 A |
|---|---|
| GW60KN-MT output current | 90 A |
| GW70KHV-MT output current | 89 A |
| Recommended AC circuit breaker (GW50KN-MT) | 100 A |
| AC cable cross-section | 25~95 mm² (50 mm² copper recommended) |
| Neutral-to-earth impedance | Less than 10 ohms |
| External leakage protection device trip current | 300 mA or higher |
| AC terminal tightening torque | 8~10 N·m |
| RS485 cable total length | Not more than 1000 m |
| Maximum stacking layers of packaging | 6 layers |
| TT grid neutral-to-earth voltage | Below 20 V RMS |
At least 5 minutes must pass after disconnecting the AC grid and DC input, so that the machine is fully discharged.
These three-phase models support TN-S, TN-C, TN-C-S and TT grid types; for TT grids the RMS voltage between neutral and earth must be below 20 V.
The total length of the cable connecting the inverter to the EzLogger Pro must not exceed 1000 m, and the communication cable must be kept apart from power lines.
The packaging can be stacked up to 6 layers maximum.