Dell EMC PowerEdge MX7000 Chassis -48 V DC Power Equipment Cabling Instructions

Dell EMC PowerEdge MX7000 Chassis Cabling Instructions for -48V DC Power Equipment Regulatory Model: E44S Regulatory Type: E44S001 October 2021 Rev. A00


Dell EMC PowerEdge MX7000 Chassis -48 V DC Power Equipment Cabling Instructions - cover page
Brand
Dell EMC
Category
Servers Computer
Document type
Installation Guide
Language
Chinese
Pages
9
File format
PDF
File size
1.6 MB
Published
10 November, 2023
Updated
10 November, 2023
MD5 checksum
54CE4FD524D5BC2894C45C5014ABAE45

About this manual

This document describes requirements and cabling instructions for the MX7000 system equipped with -48 V DC power, including power and safety ground cable routing. It covers input requirements, kit contents, required tools and cables, and assembly of the -48 V DC power input connector and cables.

The DC input requires a –(48–60) V DC SELV source electrically isolated from AC power, with maximum current consumption of 83.2 A. The instructions cover grounding cable assembly, connecting -48 V and RTN cables, installing the power cables in the chassis, and attaching ferrite fixing clips. Dell states the installation must be performed by certified service technicians. This manual is written in Chinese.

What's inside

  • About this document
  • Input requirements
  • Kit contents
  • Required tools
  • Required cables
  • Assembling -48 V DC power input connector and cables
  • Assembling and connecting safety ground cables
  • Connecting -48 V and RTN cables
  • Connecting -48 V DC power cables
  • Connecting the ferrite fixing clip

Specifications

Power supply voltage–(48–60) V DC
Maximum current consumption83.2 A
Grounding cable requirement2 AWG stranded insulated copper cable, rated at least 105 C
Branch circuit overcurrent protection100 A for DC with high interrupting current rating
DC power source requirement–(48–60) V DC SELV source electrically isolated from AC power
PSU DC-IN connector part numberPXNKY
Grounding lug kit part numberV3NR7
Rail kit part numberHC9KX
Regulatory modelE44S

Frequently asked questions

What voltage source does the -48 V DC input require?

It requires a –(48–60) V DC SELV source that is electrically isolated from AC power.

What is the maximum current consumption?

The maximum current consumption is 83.2 A.

What overcurrent protection is required?

Use branch circuit overcurrent protection rated at 100 A for DC with a high interrupting current rating.

How many grounding cable assemblies are needed per MX7000 chassis?

Each MX7000 chassis requires 2 grounding cable assemblies.