Dell EMC PowerEdge MX7000 Chassis Cabling Instructions for -48V DC Power Equipment Regulatory Model: E44S Regulatory Type: E44S001 October 2021 Rev. A00
This document describes requirements and cabling instructions for the MX7000 system equipped with -48 V DC power, including power and safety ground cable routing. It covers input requirements, kit contents, required tools and cables, and assembly of the -48 V DC power input connector and cables.
The DC input requires a –(48–60) V DC SELV source electrically isolated from AC power, with maximum current consumption of 83.2 A. The instructions cover grounding cable assembly, connecting -48 V and RTN cables, installing the power cables in the chassis, and attaching ferrite fixing clips. Dell states the installation must be performed by certified service technicians. This manual is written in Chinese.
| Power supply voltage | –(48–60) V DC |
|---|---|
| Maximum current consumption | 83.2 A |
| Grounding cable requirement | 2 AWG stranded insulated copper cable, rated at least 105 C |
| Branch circuit overcurrent protection | 100 A for DC with high interrupting current rating |
| DC power source requirement | –(48–60) V DC SELV source electrically isolated from AC power |
| PSU DC-IN connector part number | PXNKY |
| Grounding lug kit part number | V3NR7 |
| Rail kit part number | HC9KX |
| Regulatory model | E44S |
It requires a –(48–60) V DC SELV source that is electrically isolated from AC power.
The maximum current consumption is 83.2 A.
Use branch circuit overcurrent protection rated at 100 A for DC with a high interrupting current rating.
Each MX7000 chassis requires 2 grounding cable assemblies.