About this manual

The manual covers the GST I-9401 addressable sounder strobe and C-9401 conventional sounder strobe, described as optical and visual alarm devices used to warn people when fire occurs. It presents features, technical specifications, structure and operation principle, mounting and wiring, testing, and applications.

The I-9401 can be started directly by a fire alarm controller and can be electronically programmed and modified in the field with the P-9910 Hand Held Programmer. The C-9401 is powered by DC24V and can be connected to a fire alarm controller through an addressable linkage control module.

What's inside

  • General
  • Features
  • Technical Specifications
  • Structure and Operation Principle
  • Mounting and Wiring
  • Testing
  • Applications

Specifications

Signal bus voltage24 V; allowed range 16 V to 28 V
Power bus voltageDC 24 V; allowed range DC 20 V to DC 28 V
Operating currentPower standby current ≤10 mA; power alarming current ≤160 mA; loop standby current ≤0.8 mA; loop starting current ≤6.0 mA
Flashing frequency20 to 180 times per minute when alarming
Alarm sound level≥85 dB (3 m directly in front, A-weighted)
Operating environmentTemperature -10 °C to +50 °C; relative humidity ≤95%, no condensation
Dimensions144 mm × 90 mm × 57 mm
Enclosure material and colorABS, ivory white; front inlaid with plexiglass, red
Hole distance65 mm
Signal loop wiringTwisted pair; cross section ≥1.0 mm²
Power supply wiring227IEC01 wire; cross section ≥1.5 mm²

Frequently asked questions

What types of sounder strobe does GST produce?

GST produces addressable (I-9401) and conventional (C-9401) sounder strobes.

How often should the sounder strobe be tested after installation?

It should be tested at least once a year after installation and being put into operation.

How can the address code of the I-9401 be changed?

It can be electronically programmed and modified in the field with the P-9910 Hand Held Programmer.

How is the conventional sounder strobe started?

Connect DC24V to terminals D1 and D2, with D1 positive and D2 negative; the sounder strobe activates and gives audio and visual alarm.