GST GST-SCS Series Fire Emergency Evacuation Residual Pressure Monitoring System Product Manual

This manual introduces the concept of pressure difference, the necessity of fire emergency evacuation pressure monitoring system design, system composition, working principle, installation and debugging.


GST GST-SCS Series Fire Emergency Evacuation Residual Pressure Monitoring System Product Manual - cover page
Brand
GST
Category
Monitoring Equipment
Document type
Product Leaflet
Language
Chinese
Pages
8
File format
PDF
File size
1.2 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
0FA1297CCF17484F38D6B720D7EF2AA2

About this manual

The GST-SCS series is a fire emergency evacuation residual pressure monitoring system that combines industrial computer technology, communication, anti-electromagnetic interference, digital sensing technology and a fire two-bus. It uses high-sensitivity differential pressure sensors to automatically inspect and collect residual pressure changes in monitored areas 24 hours a day, issue alarm signals for over-standard residual pressure and record them.

When the residual pressure in a smoke-proof stairwell or front room exceeds the monitored value, the detector sends an alarm and the controller opens the bypass valve in the positive-pressure air supply system through the electric pressure relief air valve actuator. The system includes a monitor, controller, detector, electric pressure relief air valve actuator and dedicated monitoring software, and the document also lists design standards and technical parameters for the GST-SCS-M101 monitor and GST-SCS-C201 controller. This manual is written in Chinese.

What's inside

  • Design necessity of fire emergency evacuation residual pressure monitoring system
  • GST-SCS series fire emergency evacuation residual pressure monitoring system
  • Main features
  • Design basis and standard excerpts
  • GST-SCS-M101 fire emergency evacuation residual pressure monitor
  • GST-SCS-C201 fire emergency evacuation residual pressure controller
  • GST-SCS-PD-01/02 fire emergency evacuation residual pressure detector
  • GST-SCS-FZ-01 fire emergency evacuation electric pressure relief air valve actuator
  • GST-SCS-CD-01 fan status collector
  • GST-SCS-QG-100 fire emergency evacuation residual pressure pipe

Specifications

System capacityUp to 6400 points
GST-SCS-M101 input powerAC220V 50Hz / 150W
GST-SCS-M101 outputDC24V / 1A
GST-SCS-M101 communication distanceReliable communication up to 2000 m
GST-SCS-M101 dimensions330 mm x 160 mm x 440 mm
GST-SCS-C201 outputDC24V / 2A
GST-SCS-C201 dimensions110 mm x 90 mm x 55 mm
GST-SCS-C201 alarm threshold30-100 Pa

Frequently asked questions

What is residual pressure in this system?

It is the pressure difference between the front room or enclosed refuge floor/room and the corridor, and between the stairwell and the corridor.

What pressure difference is required between the front room and the corridor?

GB51251-2017 states a pressure difference of 25 Pa to 30 Pa.

What pressure difference is required between the stairwell and the corridor?

GB51251-2017 states a pressure difference of 40 Pa to 50 Pa.

How many residual pressure controllers can one GST-SCS-M101 monitor manage?

It can connect and manage up to 110 residual pressure controllers.

Download PDF (1.2 MB)