GST GST-N Series Fire Equipment Power Monitoring System Product Manual

The fire equipment power monitoring system is an essential subsystem of the fire alarm and control system. The system realizes effective real-time monitoring and display of the working status, undervoltage alarm information and fault information of each fire power equipment and backup power equipment in the fire control room, ensuring the normal operation of fire equipment and safeguarding fire safety.


GST GST-N Series Fire Equipment Power Monitoring System Product Manual - cover page
Brand
GST
Category
Monitoring Equipment
Document type
Product Leaflet
Language
Chinese
Pages
10
File format
PDF
File size
1.8 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
5362EA0D84BB4276CB3BC4C2DE32007E

About this manual

Chinese product manual from 海湾安全技术有限公司 (GST) for the GST-N series fire equipment power monitoring system. It describes a system built from fire equipment power status monitors and different voltage or voltage/current sensors, with sensor power and communication over a two-wire bus and optional CAN networking between monitors.

The manual covers the GST-DJ-N500 and GST-DJ-N900 monitors, the GST-DJ-D40C, GST-DJ-D44C, GST-DJ-S60C, GST-DJ-S63C and GST-DJ-S30C sensors, their functions and technical parameters, and system design, application and sensor setup. This manual is written in Chinese.

What's inside

  • Design Necessity for Fire Equipment Power Monitoring System
  • GST-N Series System Introduction
  • System Composition
  • System Functions
  • Performance Characteristics
  • GST-DJ-N500 Fire Equipment Power Status Monitor
  • GST-DJ-N900 Fire Equipment Power Status Monitor
  • GST-DJ-D40C AC Single-Phase Voltage Sensor
  • System Design and Application
  • Sensor Setup

Specifications

GST-DJ-N500 display800×480 dots, 7.0-inch color LCD
GST-DJ-N500 monitor capacityMaximum 4 bus loops, 127 coded address points per loop
GST-DJ-N500 contact output2 A/24 VDC or 1 A/125 VAC
GST-DJ-N500 dimensions420 mm × 145 mm × 444 mm (L × W × H)
GST-DJ-N500 backup powerDC 12 V/16 Ah flame-retardant sealed lead-acid battery, 2 pieces
GST-DJ-N900 monitor capacityMaximum 10 bus loops, 127 coded address points per loop
GST-DJ-N900 dimensions420 mm × 170 mm × 710 mm (L × W × H)
Operating humidity≤95% relative humidity, non-condensing
ComplianceGB 28184-2011

Frequently asked questions

What components make up the GST-N series system?

It consists of fire equipment power status monitors and different types of voltage and voltage/current sensors.

How many monitoring points does the GST-DJ-N500 support?

A single unit supports up to 4 loops totaling 508 monitoring points.

When is the GST-DJ-N900 monitor selected?

It is selected when monitoring points are greater than 508 and less than 1270.

What communication bus does the system use?

The system uses a 24 V non-polarized two-wire bus.

Download PDF (1.8 MB)

More GST Manuals