JTY-HM-GST102 line beam smoke fire detector installation and use manual, mainly introduces the overview, characteristics, technical characteristics, structural characteristics and working principle, installation and wiring, debugging, precautions, use and operation, common faults and maintenance, maintenance and maintenance, spare parts, and scrap.


GST JTY-HM-GST102 Linear Beam Smoke Fire Detector Installation and Use Manual - cover page
Brand
GST
Category
detectors
Document type
User Manual
Language
Chinese
Pages
24
File format
PDF
File size
1.1 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
28A1DED22FBFD81893D306A6859FF19D

About this manual

The JTY-HM-GST102 is a coded reflective linear infrared beam smoke fire detector from GST. The transmitter and receiver are combined in one housing, and the detector must be used with a reflector; the number of reflectors depends on the installation distance. It connects to a fire alarm controller over a bus and uses a built-in microprocessor for alarm and fault analysis.

The manual covers the detector's features, technical characteristics, structure and working principle, installation and wiring, commissioning, operation, common faults and repair, maintenance, accessories and disposal. It gives site restrictions, mounting height and position guidance, sensitivity and address setting, and maintenance procedures. This manual is written in Chinese.

What's inside

  • Overview
  • Features
  • Technical Characteristics
  • Structure and Working Principle
  • Installation and Wiring
  • Commissioning
  • Operation
  • Common Faults and Repair
  • Maintenance
  • Disposal

Specifications

Supply voltageDC 15 V to DC 28 V (power); 15 V to 28 V (bus)
Operating currentDebug ≤20 mA; standby ≤8 mA; alarm ≤12 mA; bus ≤2 mA
Adjustment angle-6° to +6°
Sensitivity levelsThree on-site levels; level 1 highest, level 3 lowest
Operating temperature-10C to +50C
Operating humidity≤95% relative humidity, non-condensing
Maximum protection area1400 m²; maximum width 14 m
Beam path length8 m to 100 m
Enclosure protectionIP20 standard; IP66 after potting
Dimensions206 mm length × 95 mm width × 95 mm thickness
Weight450 g
Housing material and colorABS, gray

Frequently asked questions

What is the beam path length range of the detector?

The beam path length is 8 m to 100 m.

How many sensitivity levels can be set on site?

Three sensitivity levels can be set on site.

What is the detector's maximum protection area?

The maximum protection area is 1400 m², with a maximum width of 14 m.

How often should the alarm function be tested?

The alarm function should be tested every six months.