GST JTY-GF-GST9711(Ex) Point Type Photoelectric Smoke Detector Installation and Use Manual

This document is the installation and use manual of JTY-GF-GST9711(Ex) point type photoelectric smoke fire detector, which introduces the product features, technical parameters, installation and wiring.


GST JTY-GF-GST9711(Ex) Point Type Photoelectric Smoke Detector Installation and Use Manual - cover page
Brand
GST
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
397 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
10328D3B64886DE4D70C162B9AB01260

About this manual

This manual provides instructions for the installation, wiring, and operation of the GST JTY-GF-GST9711(Ex) point type photoelectric smoke fire detector. The device is a non-coded detector designed for use in hazardous areas (Zone I and II) within the petrochemical and chemical industries, featuring an intrinsic safety explosion-proof type. This manual is written in Chinese.

What's inside

  • Overview
  • Technical Characteristics
  • Structure and Working Principle
  • Installation and Wiring
  • Usage and Operation
  • Application Method
  • Common Faults and Maintenance
  • Precautions

Specifications

Working VoltageDC16V~DC28V
Static Current≤60μA
Alarm Current≤30mA
Maximum Ripple Voltage4V (peak-to-peak)
Explosion Proof MarkExibIICT6Gb
Protection Area (6m-12m height)80m²
Protection Area (<6m height)60m²
Operating Temperature-10℃~+55℃
Relative Humidity≤95%
DimensionsDiameter: 100mm, Height: 54.5mm
WeightApprox. 110g

Frequently asked questions

What is the working voltage range for this detector?

The working voltage range is DC16V to DC28V.

Is this detector suitable for hazardous areas?

Yes, it is suitable for use in Zone I and II of the petrochemical and chemical industries with explosion-proof requirements.

What is the protection area for a detector in a space with a height of 6m to 12m?

The protection area is 80m² for general protection sites.

How often should a simulation fire alarm test be performed?

A simulation fire alarm test should be conducted every six months.