Fleck 3150 Downflow Water Softener Service Manual

This document is a service manual for Fleck 3150 downflow water softeners.


Fleck 3150 Downflow Water Softener Service Manual - cover page
Brand
Fleck
Category
Other products
Document type
Service Manual
Language
Spanish
Pages
40
File format
PDF
File size
2.6 MB
Published
10 November, 2023
Updated
10 November, 2023
MD5 checksum
9DECCD28F216991673271305EA3D646C

About this manual

This Spanish-language service manual covers the Fleck 3150 downflow water softener. It includes a job specification sheet, installation steps, start-up instructions, timer adjustment procedures, and control valve assembly details.

It also provides troubleshooting guidance, dimensional drawings, valve wiring information, and service assemblies for technicians maintaining the unit. This manual is written in Spanish.

What's inside

  • Job specification sheet
  • Installation
  • Start-up instructions
  • Timer adjustment procedures
  • Control valve assembly
  • Drain line flow control and brine system assembly
  • Troubleshooting
  • Dimensional drawing
  • Valve wiring
  • Service assemblies

Specifications

Minimum water pressure20 psi (1.4 bar)
Maximum water pressure125 psi (8.6 bar)
Maximum water temperature110°F (43°C)
Freezing conditionsNot permitted
Residential drain pipe minimum1/2 inch (13 mm)
Drain line for high backwash flow or long drain extension3/4 inch (19 mm)
Commercial drain pipe sizeSame as drain line flow control
Lubricant for distributor O-ringsSilicone lubricant only
Solder joint clearance from DLFCAt least 6 inches (15 cm)
Drain fitting sealantPlumbing tape only
Brine tank initial water levelAbout 1 inch (25 mm) over grid tray, or to top of air check if no grid
Power supplyUninterrupted AC
Other voltagesAvailable

Frequently asked questions

What minimum water pressure is required for the regeneration valve to work effectively?

At least 20 psi (1.4 bar) of water pressure is required.

What are the maximum water pressure and temperature limits?

Water pressure must not exceed 125 psi (8.6 bar) and water temperature must not exceed 110°F (43°C).

What drain pipe size is required for residential installations?

A minimum 1/2 inch (13 mm) drain pipe is required; use 3/4 inch (19 mm) if backwash exceeds 7 gpm (26.5 lpm) or the drain extension exceeds 20 ft (6 m).

What lubricant should be used on the distributor O-rings?

Only silicone lubricant should be used.