Models 77 and 77A are factory calibrated according to the information on the product label. They may be re-calibrated at any time to any upper temperature within the capability of the product and the sensor type used. Both upper and lower temperature may be adjusted on RTD models. See accompanying data sheet for temperature range capabilities and technical knowledge. Manufacture offers recalibration service for a nominal charge.
This operation manual covers the JENCO Model 77 and 77A two-wire temperature transmitters, which accept thermocouple (K, J, E, T) or RTD Pt-100 input and produce a 4 to 20 mA DC current output proportional to the measured temperature. It explains factory calibration, recalibration of the upper temperature (and the lower temperature on RTD models), the theory of operation, and installation precautions for non-isolated thermocouple inputs.
The manual also lists specifications for both models, the jumper-selectable measurement ranges and factory standard stock items, and includes connection diagrams with top and side views. A one-year warranty statement, return-of-items procedure and JENCO contact addresses are provided at the end.
| Output signal | 4-20 mA |
|---|---|
| Supply voltage required | 12-24 VDC |
| Output accuracy (thermocouple) | 0.1% of sensor output |
| Sensor burnout detection | 25 mA |
| Case | Gray ABS, 43 x 29 mm (1.69 diameter x 1.14 high) |
| Ambient range, model 77 | -10 to +70 °C |
| Ambient range, model 77A | -40 to +85 (as printed) |
| Lower temperature limit (4 mA), thermocouple models | Fixed at 0 °C (32 °F) |
| Lower temperature limit (4 mA), RTD models | Adjustable from -50 to +50 °C |
| Indicator | LED, brightness proportional to output |
They accept thermocouple or RTD input as indicated on the nameplate. The manual covers thermocouples K, J, E and T and RTD Pt-100.
They produce a current output in the range of 4 to 20 mA DC, proportional to the measured temperature and the calibrated upper temperature.
A supply of 12 to 24 VDC is required, and the output current can flow at any voltage between 12 and 24 VDC.
Yes, units may be re-calibrated at any time to any upper temperature within the capability of the product and sensor type; both upper and lower temperature may be adjusted on RTD models.
Jenco Instruments, Ltd. warrants the product against significant deviations in material and workmanship for one year from the date of purchase.