Rosemount TankRadar REX Radar Level Transmitter Instruction Manual 308011Pe

This document is the instruction manual for the Rosemount TankRadar Rex 308011Pe radar level transmitter.


Rosemount TankRadar REX Radar Level Transmitter Instruction Manual 308011Pe - cover page
Brand
Rosemount
Category
Other
Document type
User Manual
Language
Portuguese
Pages
34
File format
PDF
File size
1.3 MB
Published
08 November, 2023
Updated
08 November, 2023
MD5 checksum
4BA45E4576EB4F2806A254C373A93C3F

About this manual

This is the Portuguese instruction manual (Manual de Instruções, document 308011Pe, Ed.2/Rev.B, June 2008) for the Rosemount TankRadar REX radar level gauging system, published by Rosemount Tank Radar AB. It serves as a checklist guide for commissioning a REX system: verifying mechanical and electrical installations, performing calibrations and adjustments, checking communication between TRL/2 and REX units, and creating database backups.

The manual walks through checklists for the FCU (Field Communication Unit), the FBM 2180 field bus modem, the RTG 3900/3920/3930/3950/3960 tank radar gauges, and the Data Acquisition Unit (DAU), including tank measurements, still-pipe requirements, free-space requirements and REX configuration. It also covers the TankMaster WinOpi operator software and notes FCC requirements for US installations, which permit installation only in closed metallic tanks. This manual is written in Portuguese.

What's inside

  • Checks and Adjustments (Verificações e Ajustes)
  • FCU Checklist (Lista de Verificação do FCU)
  • FBM 2180 Checklist (Lista de Verificação do FBM 2180)
  • Communication Overview (Visão Geral da Comunicação)
  • RTG 3900 / 3920 / 3930 / 3950 / 3960
  • REX Configuration (Configuração REX)
  • Data Acquisition Unit (Unidade de Aquisição de Dados)
  • DAU Configuration (Configuração de DAU)
  • Operator Software - TankMaster WinOpi

Specifications

Recommended TRL/2 cable sizeAWG 20 (0.50 mm²) shielded braided cable
Max. cable length, AWG 20 (0.50 mm²)3,000 m
Max. cable length, AWG 18 (0.75 mm²)4,000 m
FCU power supply230 V default; 115 V optional

Frequently asked questions

What documents should be read before commissioning a REX system?

Before commissioning, read the Rex Installation Manual (Doc. 308014), the Rex Special Safety Instructions (Doc. 308016) and the Rex Safety Manual SIL2 (Doc. 308020).

What cable should be used for the TRL/2 field conductor?

Use a shielded braided cable with a cross-section of at least 0.50 mm²; the shield should be grounded only at the FCU.

Is the FCU intrinsically safe?

No, the FCU is not intrinsically safe and must be installed in a non-hazardous area, protected from the elements.

What is the default power supply setting for the FCU?

The switch inside the FCU box defaults to 230 V; if 115 V wiring is used, the box must be marked accordingly.