This document describes the current sensor hex busbar kits for Danfoss VLT® FC series FC 102, FC 103, FC 202 and FC 302 drives.
This Danfoss installation guide covers current sensor hex busbar kits for VLT FC series drives. The kits include parts required to install hex busbars in D1h-D8h drives, and each hex busbar is inserted through the center of a current sensor during installation.
The document lists kit numbers and supplied items, identifies hex busbar dimensions, and gives assembly steps for D1h/D3h/D5h/D6h and D2h/D4h/D7h/D8h drives. It also includes safety information on qualified personnel, electrical shock, 20-minute discharge time, electrostatic discharge, and required Nomex tubes.
| Kit 176F4181 description | 300A D1h/D3h/D5h/D6h LEM BB kit |
|---|---|
| Kit 176F4182 description | 300A D2h/D4h/D7h/D8h LEM BB kit |
| Kit 176F4183 description | 500A D2h/D4h/D7h/D8h LEM BB kit |
| Hex busbar dimensions for kit 176F4181 | V busbar: 64 mm x Ø16 mm; U/W busbars: 71 mm x Ø16 mm |
| Hex busbar dimensions for kit 176F4182 | U/V/W busbars: 49 mm x Ø19 mm |
| Hex busbar dimensions for kit 176F4183 | U/V/W busbars: 49 mm x Ø25 mm |
| Hex busbar torque for D1h/D3h/D5h/D6h drives | 9.6 Nm (85 in-lb) |
| Hex busbar torque for kit 176F4183 (500 A) | 19.1 Nm (169 in-lb) |
Torque the hex busbars to 9.6 Nm (85 in-lb).
Wait 20 minutes for the DC-link capacitors to discharge fully, then measure the voltage level to verify full discharge.
For kit 176F4183 (500 A), torque the hex busbars to 19.1 Nm (169 in-lb).
No. The heat-resistant Nomex tubes are required to maintain proper electrical protection and must not be discarded.