The DTSFU6606vbm-4G three-phase four-wire electronic multi-rate electric energy meter (DIN rail) has functions such as time-sharing measurement of electric energy, demand measurement, rate period setting, measurement of electrical parameters, closing and opening, display, 4G communication and RS485 communication. It is suitable for residential users.
The Delixi DTSFU6606vbm-4G is a three-phase four-wire electronic multi-rate energy meter in a DIN-rail case. It measures 50 Hz AC active energy in three-phase networks and provides time-of-use energy metering, maximum demand metering, tariff period setting, electrical parameter measurement, remote connect/disconnect, LCD display, 4G communication and RS485 communication. The meter is designed to GB/T 17215.321-2021, and its RS485 communication follows DL/T 645-2007.
The manual covers the design principle and the main technical parameters, then the functions: energy metering, maximum demand, electrical parameters, tariffs and time periods, data storage, event records, freeze functions, clock, 4G and RS485 communication, remote connect/disconnect, overload protection and keypad settings. It ends with the LCD display symbols and installation and wiring instructions. The built-in 4G module can only connect to the Delixi cloud platform. This manual is written in Chinese.
| Nominal voltage | 3×220/380 V |
|---|---|
| Current ranges | 0.05-0.25(6) A / 1.5(6) A with external switch; 0.25-0.5(60) A / 5(60) A with internal switch |
| Power consumption | Voltage circuit ≤2 W/10 VA; current circuit ≤1 VA |
| Clock accuracy | ≤±1 s/day from -25 °C to +60 °C; ≤±0.5 s/day at 23 °C |
| Starting current | Ist = 0.04 Itr |
| RS485 baud rates | 1200, 2400, 4800, 9600 bps; default 2400 bps |
| Data retention without power | Settlement-related data retained more than 10 years |
It is designed to GB/T 17215.321-2021, and its RS485 communication meets DL/T 645-2007.
The standard rates are 1200, 2400, 4800 and 9600 bps, and the default value is 2400 bps.
If the load power stays above the overload threshold for one minute, the meter disconnects; it reconnects automatically after 3 minutes, but after more than 6 overload trips within an hour it only closes again on a close command.
The 4G module can only connect to the Delixi cloud platform.