Delixi DDSF6606vcp Single-Phase Electronic Multi-Rate Electricity Meter User Manual

DDSF6606vcp single phase electronic multi-rate electric energy meter user manual, mainly introduces the product model, specifications, technical parameters, main functions, etc.


Delixi DDSF6606vcp Single-Phase Electronic Multi-Rate Electricity Meter User Manual - cover page
Brand
Delixi
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
9
File format
PDF
File size
862 KB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
6B27FD52D5314A74C9AE62BB41D114D7

About this manual

This is the Chinese user manual for the Delixi DDSF6606vcp single-phase electronic multi-rate electricity meter. The meter is stated to comply with GB/T 15284-2022 and GB/T 17215.321-2021 and to use the DL/T 645-2007 communication protocol. It is a 220 V, 50 Hz meter offered in the current ratings 0.25-0.5(60)A/5(60)A and 0.8-2(100)A/10(100)A with accuracy class B (class 1).

The manual covers the working principle, model and specifications, technical parameters, main functions (metering, tariffs and time periods, data storage, clearing, event records, freeze and clock), and the LCD display symbols. It then gives installation and wiring instructions with terminal screw torque values, fault diagnosis for display and metering problems, transport and storage conditions, the 36-month company warranty, and appendices listing display contents and wiring screw torque requirements. This manual is written in Chinese.

What's inside

  • Overview
  • Working Principle
  • Model and Specifications
  • Main Technical Parameters
  • Main Functions
  • Display Description
  • Installation and Wiring Method
  • Common Fault Diagnosis and Troubleshooting
  • Transportation and Storage
  • Company Warranty

Specifications

Nominal voltage220 V
Current specification0.25-0.5(60)A/5(60)A; 0.8-2(100)A/10(100)A
Operating frequency50 Hz
Starting current (active energy, class B)0.04 Itr
Infrared interface default baud rate1200 bps
RS485 interface default baud rate2400 bps
Clock accuracy at reference temperature (23 °C)≤ ±0.5 s/day
Voltage circuit power consumption≤ 2 W / 10 VA
Current circuit power consumption≤ 4.0 VA
Operating temperature-10 °C to +55 °C (level H2)
Storage temperature-25 °C to +55 °C

Frequently asked questions

How many time periods and time zones can the meter be set to?

Up to 14 time zones can be set for the year, and up to 14 time periods can be programmed within 24 hours, with a minimum interval of 15 minutes.

What communication protocol does the meter use?

Communication over the infrared and RS485 interfaces follows the DL/T 645-2007 protocol and its filed documents.

Where must the meter be installed?

To meet protection requirements the meter must be installed in a meter box or distribution cabinet, indoors in a dry and ventilated place.

What warranty does the company provide?

Within 36 months from the factory date, the company provides after-sales service if a manufacturing problem prevents normal use and the company seal is unbroken.

Download PDF (862 KB)