This product catalog introduces Siemens HB3 large current generator output circuit breaker switchgear, including product overview, typical application, customer benefits, design features, technical parameters, design, interlock, operation, connection, configuration method, selection guide, components, applicable standards, etc.
This Siemens product catalog covers the HB3 large current generator output circuit breaker switchgear for medium-voltage generator applications. It describes typical uses, customer benefits, design features, and technical data.
The document lists mechanical and electrical ratings, electrical room planning, configuration, components, and applicable standards for the HB3 switchgear. This manual is written in Chinese.
| Rated normal current (40°C, 50 Hz) | 13,500 A |
|---|---|
| Rated normal current (40°C, 60 Hz) | 12,800 A |
| Rated voltage | 17.5 kV |
| Rated voltage | 24 kV |
| Rated frequency | 50/60 Hz |
| Rated short-circuit breaking current | 110 kA |
| Rated short-circuit making current | 302 kA |
| Rated short-time withstand current (generator circuit) | 110 kA / 3 s |
| Rated peak withstand current | 302 kA |
| Protection degree | IP65 (optional IP66) |
| Width including control panel, standard phase spacing 1200 mm | 4235 mm |
| Depth | 2294 mm |
| Height, minimum/maximum | 2478/2628 mm |
| Weight, approx. (6300-10000 A) | 6200 kg |
| Weight, approx. (13500 A) | 6600 kg |
The catalog lists a rated normal current of 13,500 A at 40°C and 50 Hz.
The standard protection degree is IP65, with IP66 available as an option.
It conforms to IEC 62271-200:2011 and IEC 61936-1 (VDE 0101).
The rated short-circuit breaking current is 110 kA.
HB3 complies with service continuity loss category LSC 1.