This file is the operating manual of the EEV system, which provides the operation methods, precautions and other contents of the EEV system
This manual provides step-by-step instructions for installing and configuring CAREL E2V electronic expansion valves in HVAC systems. It covers selecting the correct valve size, installing valves with threaded or welded fittings, positioning probes, making electrical connections, and setting control parameters. Safety warnings and disposal instructions are also included.
The manual includes diagrams for refrigerant circuits, probe placement, and valve orientation. It emphasizes proper installation to avoid system malfunctions and outlines troubleshooting steps for common issues.
The valve must be sized based on the cooling capacity of the evaporator it serves. For correct selection, CAREL refers to the "E2V–E4V valve selection" manual and guided selection software on ksa.carel.com.
An undersized valve prevents reaching the desired temperature and causes high superheat, while an oversized valve can cause system swings with wide variations in temperature, pressure and superheat, or liquid returning to the compressor.
Yes, a mechanical filter must always be installed before the refrigerant inlet, both for welded valves and for valves with threaded fittings; for the latter, a filter is supplied in the packaging that fits directly in the valve inlet pipe.
The recommended connection direction has the inlet on the side of the valve, and the valves are bi-directional up to the pressure differential specified on the instruction sheet, but upside-down installation with the stator facing downwards is not allowed under any circumstances.