CAREL EVD Evolution Electronic Expansion Valve Driver User Manual

The CAREL EVD Evolution driver manual provides installation, wiring, configuration and safety information for the electronic expansion valve driver.


CAREL EVD Evolution Electronic Expansion Valve Driver User Manual - cover page
Brand
Carel
Document type
User Manual
Language
English
Pages
2
File format
PDF
File size
876 KB
Published
01 October, 2026
Updated
01 October, 2026
MD5 checksum
3C1C411BA50BD60520054FA85F4E3596

About this manual

This user manual describes the CAREL EVD Evolution electronic expansion valve driver, a PID controller for superheat regulation in refrigeration circuits. It covers the driver’s hardware, wiring diagrams, power requirements, input/output connections, and the optional display unit used for commissioning and parameter programming.

The document also details the configuration steps for network address, refrigerant type, valve type and main regulation mode, as well as safety warnings, LED indicators, and firmware update procedures. Compatibility with a wide range of refrigerants and valve models is listed, and technical specifications such as power supply limits, relay ratings and maximum cable lengths are provided.

What's inside

  • Installation
  • Wiring Diagram
  • Configuration Procedure
  • Technical Specifications
  • Safety Warnings
  • LED Indicators
  • Display Keypad Functions
  • Input and Output Connections
  • Firmware Update

Specifications

DC power supply (max cable length)24 Vdc, Lmax = 5 m
AC power supply (max cable length)24 Vac, 50/60 Hz, Lmax = 5 m
Power consumption with ALCO EX7/EX8 valves16.2 W
Relay contact rating (resistive load)5 A, 250 Vac
Maximum number of connectable drivers in a network5
Maximum RS485 cable length1000 m

Frequently asked questions

Which refrigerants are compatible with the EVD Evolution driver?

The driver supports R22, R134a, R404A, R407C, R410A, R507A, R290, R600, R600a, R717, R744, R728, R1270, R417A, R422D, R413A, R422A, R423A, R407A, R427A, R245Fa, R407F, R32, HTR01 and HTR02.

How many drivers can be connected together in a network?

Up to five drivers can be connected in a single network.

What is the maximum cable length for the RS485 communication link?

The RS485 link can be up to 1000 meters long when using shielded cable.

What voltage is used for the emergency power supply?

The emergency supply voltage is 22 Vdc ± 5 %.

Download PDF (876 KB)