Acrel ANHF Harmonic Filter Installation and Operation Manual

This instruction manual introduces the installation, use, maintenance and other related contents of Anke Rui ANHF harmonic filter, please read it carefully and keep it properly.


Acrel ANHF Harmonic Filter Installation and Operation Manual - cover page
Brand
Acrel
Category
Other products
Document type
User Manual
Language
Chinese
Pages
11
File format
PDF
File size
243 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
B2CA2309C9FE44814A4583F30BB30F6C

About this manual

ANHF is an efficient filtering device that uses high-performance filter capacitors in series with reactors to form a filter compensation system. It compensates reactive power while removing harmonic components from system current, combining dynamic reactive compensation and harmonic filtering.

The manual covers safety instructions, receiving and transport checks, referenced standards, electrical performance, cable and system installation, operating conditions, startup, daily and periodic maintenance, troubleshooting, after-sales service and the packing list. This manual is written in Chinese.

What's inside

  • Safety instructions
  • Precautions
  • ANHF introduction
  • Electrical performance
  • System installation
  • Operation
  • Maintenance
  • Troubleshooting
  • After-sales service
  • Packing list

Specifications

Working voltageAC 220V-690V
Working current20A-660A
Working frequency50/60 Hz
AC pulse voltage withstand±2500 V
Insulation classClass F, H
Total current harmonic distortion≤10% (A grade), ≤16% (B grade)
Total voltage harmonic distortion≤5%
Operating environment-10 to +45 C rated value not reduced
Protection gradeIP00-IP22
Maximum current1.5 times rated current for 60 s
Noise≤65 dB (air cooling)
Dielectric strengthIron core-winding 3000 VAC/50 Hz/5 mA/10 s, no flashover
Insulation resistance1000 VDC, ≥100 ΩA
Altitude≤1000 m
External environmentWorking temperature -10 to +45 C, relative humidity ≤90%
Working environmentNo harmful gases or flammable/explosive items; good ventilation

Frequently asked questions

What is the warranty period for the ANHF?

The product has a 2-year warranty from the factory date.

What must be done before maintaining the ANHF?

Cut all voltage and wait at least 3 minutes to ensure the capacitors are fully discharged.

What phase sequence is required for the ANHF input?

The input voltage must be positive phase sequence A-B-C.

What installation clearances are required around the filter?

Keep at least 150 mm above and below the filter and 20 mm on both sides.