Rosemount 5300 Series High Transients and ESD Installation Considerations Manual Supplement

This document is a supplement to the Rosemount 5300 Series Reference Manual and provides information on transients and how to troubleshoot them in high voltage environments.


Rosemount 5300 Series High Transients and ESD Installation Considerations Manual Supplement - cover page
Brand
Rosemount
Category
radar
Document type
Installation Guide
Language
English
Pages
8
File format
PDF
File size
766 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
D522AFEDC8002F5D5961F1BA61EFF2E4

About this manual

This manual supplement (Document No. 00809-1500-4530, Rev AA, April 2014) covers high transients and Emergency Shutdown (ESD) installation considerations for the Rosemount 5300 Series. It is a supplement to the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) and opens with safety messages for qualified personnel working on the transmitter.

For installations with high transients on Ex "d" (Flameproof) units, the document describes the built-in energy barrier, the default start-up alarm sequence, and ways to mitigate start-up alarms through grounding, galvanic isolators, and alarm delay. It then gives installation and configuration considerations for ESD systems, including the high-high unit and the low-low unit with its flange-to-upper-inlet distance and Upper Null Zone (UNZ) requirements.

What's inside

  • Safety messages
  • Installations with high transients for Ex "d" (Flameproof) units
  • Grounding
  • Isolators
  • Alarm delay
  • Installation and configuration considerations for ESD systems
  • High-high unit
  • Low-low unit
  • Start-up sequence

Specifications

Low alarm period when measurement alarm is set to low alarm20 seconds total
High alarm period during start-up (Figure 1-1)10 s
Low alarm period during start-up (Figure 1-1)10 s
Minimum distance from flange to upper inlet (low-low unit)20 in. (500 mm)
Upper Null Zone (UNZ) to be configured14 in. (350 mm)

Frequently asked questions

What does the Rosemount 5300 output during start-up?

By default the transmitter outputs both a low and a high alarm for a short period during start-up.

What happens if the measurement alarm is set to low alarm?

The high alarm period is removed and the low alarm period is stretched out for a total of 20 seconds.

How can start-up alarms caused by intermittent trips be masked?

If isolators cannot be used, an alarm delay can mask them, but it must never be longer than the calculated process safety time.

What distance is required from the flange to the upper inlet on the low-low unit?

The distance must be at least 20 in. (500 mm); if this is not met, a spool piece can be added.