This document is a supplement to the Rosemount 5300 Series Reference Manual and provides information on transients and how to troubleshoot them in high voltage environments.
This manual supplement (Document No. 00809-1500-4530, Rev AA, April 2014) covers high transients and Emergency Shutdown (ESD) installation considerations for the Rosemount 5300 Series. It is a supplement to the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) and opens with safety messages for qualified personnel working on the transmitter.
For installations with high transients on Ex "d" (Flameproof) units, the document describes the built-in energy barrier, the default start-up alarm sequence, and ways to mitigate start-up alarms through grounding, galvanic isolators, and alarm delay. It then gives installation and configuration considerations for ESD systems, including the high-high unit and the low-low unit with its flange-to-upper-inlet distance and Upper Null Zone (UNZ) requirements.
| Low alarm period when measurement alarm is set to low alarm | 20 seconds total |
|---|---|
| High alarm period during start-up (Figure 1-1) | 10 s |
| Low alarm period during start-up (Figure 1-1) | 10 s |
| Minimum distance from flange to upper inlet (low-low unit) | 20 in. (500 mm) |
| Upper Null Zone (UNZ) to be configured | 14 in. (350 mm) |
By default the transmitter outputs both a low and a high alarm for a short period during start-up.
The high alarm period is removed and the low alarm period is stretched out for a total of 20 seconds.
If isolators cannot be used, an alarm delay can mask them, but it must never be longer than the calculated process safety time.
The distance must be at least 20 in. (500 mm); if this is not met, a spool piece can be added.