YTC YT-1000L Electric Valve Positioner User Manual

YT-1000L electric valve positioner manual, introduces product features, type selection codes, main parameters, structure diagrams, operating principles, external dimensions, installation, piping, power connection, adjustment, product maintenance and inspection, fault diagnosis and measures


YTC YT-1000L Electric Valve Positioner User Manual - cover page
Brand
YTC
Category
Electro-Pneumatic Positioner
Document type
User Manual
Language
Chinese
Pages
22
File format
PDF
File size
1.2 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
87C4E3E0033A751161E51A0B337EAF22

About this manual

The YTC YT-1000L series is an electric valve positioner that receives a 4–20 mA DC signal from a control system and precisely adjusts valve opening. Model codes cover single-acting and double-acting versions, explosion-proof and non-explosion-proof types, feedback lever ranges, orifice options, air connections and temperature options.

The manual covers safety and use precautions, nameplate contents, features, model code, main specifications, structure and operating principle, dimensions, installation with a bracket, piping, power connection for explosion-proof and intrinsically safe types, zero/span and orifice adjustment, maintenance and inspection, and troubleshooting. Listed specifications include a 10–150 mm stroke, 1.4–7.0 kgf/cm² (20–100 psi) supply pressure, IP66 protection, a die-cast aluminum body and a 2.7 kg weight. This manual is written in Chinese.

What's inside

  • Safety precautions
  • Product introduction
  • Nameplate contents
  • Features
  • Model code
  • Main specifications
  • Structure and operating principle
  • Installation
  • Piping
  • Adjustment and maintenance

Specifications

Input signal4–20 mA DC
Impedance250 ±15 Ω
Supply pressure1.4–7.0 kgf/cm² (20–100 psi)
Stroke10–150 mm
Air connection sizePT (NPT) 1/4
Power connection sizePF 1/2 or G 1/2
Explosion protection (KTL)ExdmIIBT5, ExdmIICT5, ExiaIIBT6
Enclosure ratingIP66
Linearity±1.0% F.S
Repeatability±0.5% F.S
Air consumption3 LPM at supply 1.4 kgf/cm², 20 psi
Flow80 LPM at supply 1.4 kgf/cm², 20 psi
Weight2.7 kg (6.1 lb)

Frequently asked questions

What input signal does the YT-1000L accept?

It accepts a 4–20 mA DC input signal.

What supply pressure range does the YT-1000L use?

It uses a supply pressure range of 1.4 to 7.0 kgf/cm² (20 to 100 psi).

Does the YT-1000L come in single-acting and double-acting versions?

Yes. The model code uses S for single acting and D for double acting.

What is the enclosure protection rating?

The listed protection rating is IP66.

Download PDF (1.2 MB)

More YTC Manuals