This user manual for the YTC YTC8750 describes operation, safety precautions, and technical specifications for a multifunctional instrument used to test…
The YTC YTC8750 CT Volt-Ampere Ratio Polarity Tester is a multifunctional field testing instrument designed specifically for testing current transformers. It performs functions such as volt-ampere characteristics, ratio, polarity, error curve calculation, knee point determination, and secondary circuit checks. The device features automatic voltage/current rise, data storage, USB connectivity, and on-site printing capabilities to improve work efficiency. This manual is written in Chinese.
| Operating Power Supply | AC220V (50 ~60Hz) |
|---|---|
| Volt-Ampere Output Voltage | 0~1000V |
| Volt-Ampere Output Current | 0~15 A |
| Ratio Output Current | 0~600 A |
| Volt-Ampere Measurement Accuracy | ≤ 0.5% |
| Ratio Measurement Accuracy | ≤ 0.5% |
| Operating Temperature | -10~50℃ |
| Weight | ≤18Kg |
The product comes with a three-year free repair warranty and lifetime paid maintenance thereafter.
Users must read the manual carefully, ensure the instrument is grounded, and disconnect all connections on the transformer terminals before testing.
High voltage may be generated in the secondary, so non-tested windings must be short-circuited.