Rotork 1400/1600 Series and IQ Mk1/Mk2 Valve Actuator Setup Guide for Black Liquor Recovery Boilers

This document provides recommendations for setting up Rotork valve actuators on rapid drain valves and feed water stop valves on Black Liquor recovery boilers


Rotork 1400/1600 Series and IQ Mk1/Mk2 Valve Actuator Setup Guide for Black Liquor Recovery Boilers - cover page
Brand
Rotork
Category
Automation control Equipment
Document type
Application Note
Language
English
Pages
26
File format
PDF
File size
1.8 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
DF4542C150F292E479B2E191E3490D4D

About this manual

This Rotork document is a guide and set of recommendations for setting up Rotork electric valve actuators on rapid drain valves and feed water stop valves on black liquor recovery boilers, where the requirements are described as quite specific as defined in BLRBAC good practice. It opens with a history of Rotork supply to these boilers, from the hardwired 1400 Series on the A range actuator through the 1600 Series with solid state controls to the IQ series and the IQ Mk. 2 introduced in 2000.

Later sections answer common questions about IQ battery and ESD/ESP functions, give a decision table for remedial action after a power interruption on IQ Mk1 and Mk2, describe battery change out procedures, and set out a matrix of features comparing the 1400, 1600, IQ Mk 1 and IQ Mk 2. Settings, wiring connections and wiring diagrams are covered in four subsections: 1400 Series, 1600 Series with optional local stop override, IQ Mk1 with optional local stop override, and IQ Mk. 2. Installation and maintenance instructions are referenced to publications E270E, E170E and E170E2.

What's inside

  • Rotork Supply History
  • Clarification of Application of the IQ Mk. 1 and Mk. 2
  • Decision Table IQ Mk1 and Mk2
  • Battery Change Out Procedure for IQ Mk1 Actuators
  • Battery Change Out Procedure for IQ Mk2 Actuators
  • Matrix of Features
  • Settings and Wiring Connections – 1400 Series
  • Settings and Wiring Connections – 1600 Series with optional local stop override
  • Settings and Wiring Connections – IQ Mk1 with optional local stop override
  • Settings and Wiring Connections – IQ Mk. 2

Specifications

Battery typeUltralife U9VL lithium manganese dioxide battery (equivalent 9V battery allowed for watertight enclosures)
Battery shelf lifeSeven years
Recommended battery replacement intervalEvery three to five years
Settings storageNon-volatile RAM; settings survive a complete power loss
Stall timerFitted on IQ Mk1 and IQ Mk2; can be bypassed by setting it to a maximum time

Frequently asked questions

Why does Rotork use a battery in its IQ actuators?

The battery provides back up power for the LCD display and the remote position indicating relays when main AC power is lost, and it updates the position processor if the valve is operated manually during an outage.

Will the settings be lost if the battery is changed with power down?

No. The settings and the end of travel position are not affected, provided the actuator is not moved during the battery change out.

How often do the batteries need to be changed?

The recommendation is that batteries be changed every three to five years; the shelf life of a battery is seven years.

Can the ESD override external interlocks?

According to the matrix of features, the 1400 series A range hookup will bypass interlocks, the IQ Mk. 2 can be programmed to override them, and the IQ Mk. 1 and 1600 series A range need external field wiring.