Rotork Q Range Electric Direct-Drive Quarter Turn Valve Actuators Instruction Manual

This document is the instruction manual for ‘Q’ Range electric direct-drive quarter turn valve actuators, which is manufactured by Rotork. It is mainly used in industrial scenarios.


Rotork Q Range Electric Direct-Drive Quarter Turn Valve Actuators Instruction Manual - cover page
Brand
Rotork
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
12
File format
PDF
File size
1.2 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
B9922EC8DB1E1FF58D21EA76B0BD1F92

About this manual

This instruction manual is for the Rotork Q Range electric direct-drive quarter turn valve actuators. It is written to enable a competent user to install, operate, adjust, and inspect the actuators, and it identifies actuator parts and gives mounting and setting instructions.

The document covers the drive bush, mounting onto a valve, mechanical stops, electrical wiring-up, switch settings, selection of remote control functions, replacement of the top cover and indication, optional extras, and lubrication and maintenance. It includes warnings on safe lifting, electrical isolation, and handwheel operation.

What's inside

  • Identifying Actuator Parts
  • Mounting Actuator and Setting Instructions
  • Drive Bush
  • Setting Mechanical Stops
  • Electrical Wiring-Up
  • Switch Settings
  • Selection of Remote Control Functions
  • Replacement of Top Cover and Indication
  • Optional Extras
  • Lubrication and Maintenance

Specifications

Mechanical stop setting range80° to 100° of output movement
Cable entriesTwo cable entries for power and control cables
Auxiliary switchesTwo or four auxiliary switches available, depending on electrical specification
Torque outputFactory set to maximum rated torque in both directions
Drive bushSteel drive bush supplied blank
Top cover fixingSecured with 6 fixing bolts
Terminal cover fixingSecured with four fixing screws

Frequently asked questions

What are the Q Range actuators designed to stop on at each end of travel?

They are designed to stop on torque at each end of travel onto the mechanical stop bolts.

How do you engage the handwheel for manual operation?

Pull the hand auto lever up towards the handwheel.

How many cable entries does the actuator have?

It has two cable entries for power and control cables.

Which auxiliary switches are suggested for remote end-of-travel indication?

The lower pair, Close Aux Switch (CAS) and Open Aux Switch (OAS), are suggested.

Download PDF (1.2 MB)

More Rotork Manuals