This manual provides detailed information on the product selection, technical characteristics, size and installation method, product communication method and wiring, troubleshooting, etc. of the concentrated power concentrated control fire emergency sign lamp.
This installation and operation manual (V1.0) covers the Acrel 309 concentrated-power, concentrated-control fire emergency sign luminaires in wall-mounted (single-sided) form. The signs guide people along evacuation routes; their status is sent over a communication line to a distribution unit, which passes the data to the emergency lighting controller that manages them. On-site addressing is done with the company's electronic encoder.
The manual lists the A401 series (DC36V) and A431 series (DC36V or DC24V) models for exit, left, right, bi-directional and floor indication, and gives technical characteristics such as power below 1 W, LED light source, emergency time over 90 min, fault detection and 1 Hz ±10% flash frequency. It also covers dimensions and wall mounting, two-wire non-polarized communication wiring, and a short troubleshooting table. This manual is written in Chinese.
| Power consumption | Less than 1 W |
|---|---|
| Light source type | LED |
| Emergency time | Greater than 90 min |
| Flash frequency | 1 Hz ±10% |
| Encoding | Electronic encoding, occupies one address |
| Operating environment | Temperature 0 °C to +55 °C; relative humidity ≤95%, non-condensing; indoor use |
| Housing material and color | Aluminum alloy (natural color) |
| Protection rating | IP30 |
| Dimensions | 400 × 160 × 16 mm (H × W × D) |
| Communication | Two-wire bus, non-polarized |
| Communication cable | NH-RVSP-2*2.5mm² |
| Standard | GB17945-2010 |
It is wall mounted: the plastic anchors and screws are fixed to the wall first, then the wall-mounting holes on the back plate of the sign are aligned with the screws and hung on the wall.
NH-RVSP-2*2.5mm² cable, routed separately from power cables and high/low-voltage distribution cables, not in the same conduit or trunking.
Check with a multimeter whether 24V/36V power is present at the luminaire; if not, the power supply is lost and the correct wiring between the distribution unit and the luminaire must be restored.
It uses electronic encoding and can be coded on site with the electronic encoder produced by the company, occupying one address.