This manual provides detailed information on the product selection, technical characteristics, size and installation method, product communication method and wiring, troubleshooting, etc. of the concentrated power concentrated control fire emergency sign lamp.


Acrel 309 Concentrated Power Concentrated Control Fire Emergency Sign Luminaire Installation Manual - cover page
Brand
Acrel
Category
lighting
Document type
Installation Guide
Language
Chinese
Pages
5
File format
PDF
File size
550 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
0D7231A400EB61FFA39A5AC5384A336B

About this manual

This installation and operation manual (V1.0) covers the Acrel 309 concentrated-power, concentrated-control fire emergency sign luminaires in wall-mounted (single-sided) form. The signs guide people along evacuation routes; their status is sent over a communication line to a distribution unit, which passes the data to the emergency lighting controller that manages them. On-site addressing is done with the company's electronic encoder.

The manual lists the A401 series (DC36V) and A431 series (DC36V or DC24V) models for exit, left, right, bi-directional and floor indication, and gives technical characteristics such as power below 1 W, LED light source, emergency time over 90 min, fault detection and 1 Hz ±10% flash frequency. It also covers dimensions and wall mounting, two-wire non-polarized communication wiring, and a short troubleshooting table. This manual is written in Chinese.

What's inside

  • 概述 (Overview)
  • 产品选型 (Product Selection)
  • 技术特性 (Technical Characteristics)
  • 尺寸与安装方式 (Dimensions and Installation)
  • 产品通讯方式与布线 (Communication Method and Wiring)
  • 故障处理 (Fault Handling)

Specifications

Power consumptionLess than 1 W
Light source typeLED
Emergency timeGreater than 90 min
Flash frequency1 Hz ±10%
EncodingElectronic encoding, occupies one address
Operating environmentTemperature 0 °C to +55 °C; relative humidity ≤95%, non-condensing; indoor use
Housing material and colorAluminum alloy (natural color)
Protection ratingIP30
Dimensions400 × 160 × 16 mm (H × W × D)
CommunicationTwo-wire bus, non-polarized
Communication cableNH-RVSP-2*2.5mm²
StandardGB17945-2010

Frequently asked questions

How is the Acrel 309 sign luminaire mounted?

It is wall mounted: the plastic anchors and screws are fixed to the wall first, then the wall-mounting holes on the back plate of the sign are aligned with the screws and hung on the wall.

What cable is required for the communication line?

NH-RVSP-2*2.5mm² cable, routed separately from power cables and high/low-voltage distribution cables, not in the same conduit or trunking.

What should be done if the luminaire does not light?

Check with a multimeter whether 24V/36V power is present at the luminaire; if not, the power supply is lost and the correct wiring between the distribution unit and the luminaire must be restored.

How is the sign luminaire addressed?

It uses electronic encoding and can be coded on site with the electronic encoder produced by the company, occupying one address.